why there is a temperature rise at different metal to metal
contact at cable lug??suppose cable is aluminium and the lug
is copper,than why the temperature rise takes place??
Answer Posted / nagesh.patwari
Galvanic corrosion-
As moisture can easily enter to the termination point, aluminium conductor, as a reactive metal in
galvanic series, is susceptible to corrosion when aluminium comes into contact with a more stable
material, such as the relatively noble metal copper. Galvanic corrosion is a typical issue for
30
aluminium conductor when dissimilar metals are in contact with each other in the presence of
electrolyte. Such deterioration of aluminium can not only accelerate the depletion of conductor, but
also affect the contact behaviour and promote the contact failure.
The use of dissimilar metals at the termination point is also not good at coping with thermal shock
or high temperature condition which generates incompatible thermal expansions of conductor and
terminal, since aluminium has a relatively high coefficient of expansion than common terminal
metals such as copper metal. Incompatible mechanical/thermal behaviours between terminals and
aluminium conductors deteriorate the connection and eventually cause a failure since dynamic
loads or vibration can be existing over a long time period
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Readings of ER300P Trivector meter
What is the feedback in the control system?
What is evaporator & condencer & compressor
what is laser diodes?
what are the steps involved in generator load test?
how define the torque in ac drive. from electrical side in the drive friquency ,voltage and current three factor is there.
Differentiate between magnetic field and magnetic flux?
What is frantic effect?
what is Insulation monitoring device. where it is used? (in switchgear room or control panel or in field equipment)
Explain about how is it working Earth fault'relay and wahts the resistance value of earth bed
what happened when we supply a dc current in dc motor?? can it worked properly?
any application of back emf
CALCULATE THE TOTAL VOLTAGE DROP AND SELECT THE CABLE SIZE IN MM-SQARE FOR A PANEL-262KW AT 110 METER FROM THE SOURCE SUPPLY , SUPPLY VOLTAGE 240/415
after how many spot we must chang secondry cable in portable spot welding gun?
Define relative stability.