Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

The armature of shunt dc motor has 0.8ohm resistance and motor
is to run on 120V circuit.If motor is suddenly thrown on
circuit while armature at standstill then current drawn by
motor will be??Also back emf in normal running is 110V

Answer Posted / muhammad waqas

V =Eb + IaRa
Ra= 0.8ohm
Eb=110V
V=120V
Put values in eqn
120-110=0.8Ia
10/0.8= Ia
Ia = 12.5 A

Is This Answer Correct ?    5 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

im working in one private compeny in gujarat. i was complet diploma electric in 2010 from gujarat technical board. now i want electric supervisor licence in gujarat but i dont't know when i apply? plz give me address of the licence dippartment office in gujarat. gandhinagar

1914


In CTs tan delta point should be earthed , what is the reason behind it?

3088


what are the pecularity of shaver sockets ?

1969


What is difference between Harmonic and Non harmonic Capacitor Bank?

2977


what is PID control in VFD drives?

2070


what is the advantage of connecting capacitors in delta than in star?

2157


what is the use of the circle diagram

5746


Give some differences between open loop and closed loop?

1167


3phase cable calculation formula by motor load

1577


What consists of 2 or more thermocouples to be connented series?

2376


what is mean by dual digital protection in the relay field?

1987


Consider three heater bank connected in 3 phase star with neutral.Each heater bank connected in each phase.So each phase get 230 volts supply.my question is,during balance condition, current flow in neutral or Not

1698


If a transformer primary winding operates at 240v, the secondary at 120v and the load is 1500w & the transformer is rated at 92% efficient, what's the current flowing through the primary winding of the transformer? What is the formula for finding this?

2254


any one can explain the stages of a knee point which is taken during ct magnetising curve.

1820


What is the alternate solution for testing of polarity by using polarity tester while its milli ammeter does not works?

2084