Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the function of NAT & NAC contacts in breaker
control switch (TNC)??

Answer Posted / rajesh t k

The NAT and NAC contacts are provided on TNC switch to facilitate additional functionalities from the TNC switch than mere Tripping or Closing.


These contacts are also known as Lost Motion Contacts. They help identify the last operation (Trip/Close) performed by the operator through the TNC switch.

The NAC contact will be closed whenever the operator turns the TNC lever to Close position and the contacts stays closed even after the lever is returned to the Neutral position by the operator, until the lever is turned to Trip side.

Hence, the 'Auto Trip' indication can be given via the NAC contact(instead of giving through an NO contact of the master trip relay), in series with the CB's 52b contact. That is, this is just an alternate way to wire up the 'Auto Trip' indication.

The NAT contact, likewise will be through whenever the CB has tripped via the TNC lever switch by the operator, until the lever is turned to Close position again.

Is This Answer Correct ?    12 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the formula of starting current of 3phase and 1 phase motor???

2076


what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?

7982


What is the temperature PROFILE OF A FLUID W. R. T. Distance from a sphere to which it is IN CONTACT which is at constant temp.?

2055


defult setting in p220 micom motor proction relay for 11kv,640kw,f.l.a.-40a,1440rpm ht motor?

3697


can anyone show me how the 3 phase power is supplied to socket outlets?

2017


What is Antipumping Function & If we have C.T how we find the Ratio ?

2022


What do you mean by pull of electromagnet?

1032


I have experienced electrical maintenance HT ,but I completed be ECE ....can I apply c license or not ???? Pls help me friend s...

1567


following are the questions asked in interviews: 1) Considering the short circuit fault, which switchgear is preferable, SFU OR MCCB? Which operates faster? whicg one is popular in Indian Market and why? 2)Define SCPD. What is type2 coodination? 3)Why the contactor rating is higher for the fuseless selection than for fuse selection? whether the ratinf of SFU or MCCB remains the same in both the cases? 4)If the HP rating is known then can you calculate the ratings of L.V Switchgear(SFU/MCCB, contactor, OLR) without using the selection chart?

2055


In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.

2106


Can we Co-ordinate relay in Load Break switch?

1956


how to convert lv line to hv line and viseversa, any losses will occur during this process

2068


PIU how does work?

2428


What should be the Sandwitch type Al. bus bar capacity for 2 M.W.Gen. set, having continuous full load current- 3463 Amps,ambient temp.- 50 Deg. C., Required temp. raise-20 deg.C., it will run 24 hrs, 365 days on full load, required highly reliable.

2673


HOW TO CALCULATE THE REGULATION OF 100 AND 25 KVA TRANSFORMER

1972