2 electric bulbs of 100w,200V are put in series & the
combination of each bulb is supplied to 100 V . the power
consumption of each bulb will be????????
Answer Posted / mudasar marwat
R=V^2/P = 200^2/100 = 400 ohm
power consumed by each bulb is calculated by the same expression
P=V^2/R
but here the voltage is equally divided between two bulb which is 50 now across each
so P=50^2/400 =6.25 w
| Is This Answer Correct ? | 24 Yes | 4 No |
Post New Answer View All Answers
What are the main faults of DC generators?
Whether amorphous core transformer is commercialized or not:Name of company making amorphous core transformer and what are different rating?
How do you calculate the actual power consumption of an inductive load appliance. Say, a deep freezer of 200watts
what is the differencce inn series and cascade connection??
errection check list for transformer maintenance
exolain the star delta connection
What is the rating factor for copper cable ( Specific value according to the type of laying ) & the voltage drop?
63MVA,220KV/6.9KV Transformer LV side neutral is connected to Earth pit through NGR. Whether this earth pit required to connect with near by below grouding earth mat or it is to be kept separate?
What is meant by derating factor?
I am doing apprenticeship training at HT switch yard in NLC. How can i get electrical c license. ??? What r the rules for getting it as an apprentice? ??
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA
why the difference arise between HT reading & LT reading (submeters fixed in complexes, apartments etc)if the power factos exceed from 0.9 to 1 can the ht meter reads fast?
How much kv gas generator is needed to run 2 hp and 1 hp airconditioners, plus a refrigerator and 4 Tvs
what questions will be asked for 11/33KV licence interview APSEB hyderabad. Can any one share question and answers.
Hi everyone. Some Generators uses 3-Pole breakers with extra contactors for Neutral. Some uses 4-Pole. Why so? What is the idea behind this? Thanks in advance for the solution. Kr.