A 200W,230V lamp is connected across 115V supply.The lamp will
draw power?
Answer Posted / sachin prajapati
(1) R=V1^2/P=230^2/200=264.5
V2=115
P=V2^2/R=115^2/264.5=50W
(2) R=264.5
I2=V2/R=115/264.5=0.435
P=V2I2=115×0.435=50.025W
So answer can both
| Is This Answer Correct ? | 6 Yes | 5 No |
Post New Answer View All Answers
what is the IEC standard for Power Cable installation in onshore (like in direct buried ground or above groung)
what is meant by LCR meter? where its useful ?
what is mean by PIR in circuitbreaker and give me detail of that?
Show Details FROM:Muhammed Ikram TO:qa@allinterview.com Message flagged Saturday, June 4, 2011 10:07 PMMessage bodyHello all, i want to ask a question to all of you that what is VMM (voltage monitoring module )? how it work,s? i heard somewhere that it compare 1 phase voltage to other phase voltage. but there is also some setting on it. how to set it,s setting. please tell me briefly. Thank,s and Regard,s. Muhammed Ikram.
best manufacturer for busbar for outdoor switchyard having double bus bar scheme, can any one share technical specification of busbar. 132kv voltage ?
As we know induction squirrel cage motor torque Directly praprortinal to applied voltage in star connection & delta also. If I connect 55KW Motor to DOL starter in load condition does motor withstand the load & what will be the current withdrawn ? motor will not fail ?
where we use the SFU & FSU?
What happened if C.T mount at any cable or Bus bar in wrong direction . C.T going on proper work or not . C,T direction is essential thing to properly work.
critically criticize the application of ring main unit in power system
Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example?
what is RFID? thire application;
why the protection turbo generators is most complex?
why we change the direction of winding in rotor ?how we make the north and south pole?
how to find Harmonics and types as per the equipemnts
i want bhel placement paper for electrical if anybody having pl send to my id kavitha867@myway.com immediately