What is the difference between EXE and EXD

Answer Posted / aris

There is a lot of confusion when it comes to “flameproof” products. Ex d or “Flameproof” means that an enclosure or junction box is constructed and certified as Explosion Protected according to the “Flameproof” standard. The “Flameproof” philosophy is that should an explosion occur within the enclosure, it will either be contained or the escaping flame will be cooled by a “flame-path” thus mitigating the risk of igniting an explosive outside atmosphere. Other equipment designated flameproof, like a flameproof cable gland, is constructed in such a way that it will maintain the flameproof integrity of a flameproof enclosure to which it is fitted. Ex e, on the other hand, means that the enclosure is constructed and certified as “Explosion Protected” according to the “Increased Safety” standard. The philosophy with Ex e is to provide an impact resistant enclosure and also to ensure that its contents are certified such that they will never produce sparks or temperatures or current creepage that could ignite the flammable atmosphere which may enter the enclosure. Ex e rated enclosures are therefore explosion protected but are not “Flameproof”. In selecting both Ex d or Ex e equipment it is necessary to ensure the Temperature “T”-rating and the gas group certification is appropriate for the specific prevailing flammable atmosphere. Both Ex e and Ex d junction boxes can be used on Zone 1 areas. Ex d Flameproof boxes are normally manufactured from heavy patterned cast iron and are generally also suitable for use underground in coal mines. Ex e Increased Safety boxes are normally manufactured from an engineered plastic and are generally suitable for surface applications and in non-fiery mines. Ex e is usually a less expensive method of protection than Ex d. We are always here to help or give advice if you are not sure

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the Nyquist criterion regarding control systems?

663


What will happen if i used 11KV earth ht kit to 11 KV / 11 KV cable termination?

998


What are test values for an 63 KVA and 100 Kva Distribution Transformers for the following typical tests 1)Magnetic balance 2)Short circuit test 3)Open Circuit test 4)Vector group confirmation test .please give me the standard values for all the above tests.

2279


WHAT IS MEANING OF Gg & Gg IN hrc FUSE

2847


In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.

1143






would you please give me any idea about the BARC interview question on electrical? i have an interview on 1st july.....plz hlp me.......its urgent......

2029


How to calibrate or test an LT Air Circuit breaker 440 volts, 35 KA, 800 Amps ?

1514


11 kV line deraction check by an Engineer.

1525


Explain advantages of storage batteries

655


why any centrifugal blower draw more current in starting. consider id fan and fd fan?

1375


What are the types of control system?

636


On 400 amp factory load how kvarh capacitors provide

1296


-What shall be short circuit current of LV switchgear for a 1000 kva, 11.415kv, 3 phase tranformer with 5% reactance.

1682


What is the restart inhabit setting in ABB spam150c relay (Motor protection relay)

3049


Define what is difference between fuse and breaker?

675