A cylindrical wire is compressed in length by 10%. The
percentage decrease in the resistance will be?????
Answer Posted / ali asghar
As we know
R= p*L/A
if resistance decreased by 10 % it mean new resistance is
L'=0.9L
And Area is increased by 10 % because volume will remain constant so new area will be
A' = 1.1A
so
R'=p* .9L/1.1A =.9R/1.1=0.81R
so change in resistance is = 1-0.81=0.91=0.91*100 %= 19 %
so resistance decreased by 19%
| Is This Answer Correct ? | 55 Yes | 9 No |
Post New Answer View All Answers
Why we used 690V in ACS 800 drives.Why dont use standard voltage like 415v or 1.1Kv
Define non-touching loop.
how many types are their in switchyard or substation(like D,I TYPE), what is differant between them
can u describe the method used for protection of transmission line.
what is the diference between the 4pole & 6pole DC Motors & what is advantage 6pole over the 4pole ?
If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.
when ac current flows thru d coil of a contactr,it energizes,magnetic field attracts d contact of the coil...nw wont dt ac current in d contct induce current back on to d coil thru mutual inductance leading to high currnt in d coil
Can any one give an explanation about rating factors of cable? if we are laying the cable on the air with an temp 15 degree then rating factors will be 1.15 and if we are laying the cable on the air an temp 60 degree then rating factor will be 0.76 please describe it and what is the difference between rating factor and derating factor?
What is the difference between Static and servo controlled voltage stablizer?
what is meant by the phrase 'static load' in case of shorting in a generator excitation system?
I have 2 KW electric water heater.I am gonna use it in controlling water temp.so I needed to increase or decrease the heating capacity.is there any electrical-electronic circuit for varying the resistance & so current?
solar inverters was not connected to the nuteral link .this nutwral possible to any other systems
how to make an earthing certificate
Grid fault level [KA]?
If mutual flux is 1.2wb & power factor is 0.8 lag , then what is the Useful flux of a transformer?