What are the different protection systems used to protect
the transformer internally and externally?
Answer Posted / vinod g
Transformer protection
1) protection provided in the transformer are
A) buchholz relay for both main and oltc (ansi no 63)(alarm and trip)
B) winding temperature (wti) 49(alarm and trip)
C) oil temperature (oti) 49 (alarm and trip)
D) explosion vent or prv
e) Magnetic oil level gauge for alarm
f) Fire protection (Mulsifire system)
g) Lightning Arrester provided in both HV and LV
2) High Voltage side Protection
a) differential protection 87 (operate when fault occurs between HT CT and LV CT)
b) REF restricted earth fault 64 for winding protection
c) over flux for higher rating transformer
d) directional over current towards the source side, operate when fault feeding from LV during coupled with other transformer
NOTE: Master trip 86 relay is provided as the above relays are having less current rating output contacts, can not provide sufficient current huge trip coil circuit breaker. also 86 is provided with manual reset
3) Low voltage side Protection
Instantaneous and time delay over current 50
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the unit of attenuation?
Is it possible to make a 5P10/ CT Ratio 50/1A Burden 5VA
how to calculate the earth fault current
EHV current carrying parts need to have smooth finish,then how can a 245kv GIS with emery finish can run so long?
how can i find cable size from current rating?
if field breaker of generator is closed prior to its rated speed on a power generating unit. what will be the effect on generator, unit transformer and starting transformer.
What is phenomenon of electromagnetic induction and how it works?
What is the earth treantment procedure?
Which contains in POLE ASSEMBLY of a 11KV Kirloskar-make SF6 (Model No-FP620A12)? Will u clarify with drawing?
distribution transformer de-rating formula on over limit iron losses
ITI r/tv trade APPLY (J.T.O VACANCEY) ALSO INCLUD AITT ELECTRONIC,WRITEEN XAM DONE 23.03.10 BUT NO RESPONCE WHY ANATHER ID gopal_gh007@rediffmail.com
11kV capacitor bank of rating 2.4KVAR, is charged with protective relays of only over current & Earth fault &.......without Over Voltage, Under Voltage & Neutral Displacement Relay. Is it advisable??
where we use the SFU & FSU?
What are motor generator sets and explain the different ways the motor generator set can be used ?
what are the major & minor faults that occur in an inverter and in UPS ? And how to repair and resolve them ?