Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

As we know multiplicity factor derivation equation is as below
MF = main c t ratio / main p t ratio * meter c t ratio / meter p t ratio * meter dial constant
Where in digital meters for HT kwh import export now a days meter constant are calibrated already which is 1
So my question is For HT 11kv 110 v line values are as below
Main c t and p t ratio are 11000 v and 110 v and 20/5 means 20 amp and 5 amp
Now meter values are 11000/√3/110√3 and primary and secondary amp are displayed as -/5 amp on kwh meter so what will be the MF for this meter ?

Answer Posted / sameer

As i know it will be as below if wrong kindly solve it
MF=
11000/100*20/5/11000/110*5/5=4
Where meter ratings are -/5amp so i have taken primary and secondary both current 5 amp m i right ???????

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Draw a SLD for main panel for school having connected load of 1200kw and emergency generator 200kw.also show the increase of additional load of chiller 225kw in the lv panel indicating meter postion size of transformer ,cables and capacitor bank.

984


which IS or IEC is used for earthing,breakdown voltage of transformer oil, hv/pd testing and all type of electrical testing

2623


what a function diesel generetaor turbo charger & turbo charger is more heated explain reason ?

2262


how generator load test is conducted?what are the steps?

1610


Differenciate between circuit wiring and sub main wiring with illustrations

2257


What is the estimated total hydropower potential of india?

1144


how much value of resistance should connect to 15 kw, 6 pole 3 phase slip ring induction motor having RV-240, RA-42.

1924


what is the difference b/w ATS and HTS?

2199


Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output

1847


Does magnetomonopoles exists? one maxwell equation strongly suggests no, but how about their existance in plasma?

2012


describe the phenomena of vacuum interruption in C.B

1798


In which of the following case, the rotating magnetic field is reversed? A regenerative breaking B plugging C dynamic breaking D forward motoring

1979


What is the difference between a 3 winding and 2 winding Potential Transformer

2295


what is physical distance of isolator to VCB in 33/11kv sub stations

2143


The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.

1989