I am applied 100 % pressure on to the air to open control valve,but the valve is not fully closed..and 10-15% is open the valve. how to calibrate the control valve?
Answer Posted / oliver
in postioner there are span and zero setting. with the help of span n zero we can adjust it.
if your valve is not fully close than use zero setting, and if it is not fully open than use span setting.
Is This Answer Correct ? | 2 Yes | 0 No |