Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is fuction of NGT/NGR using in Generator.

Answer Posted / avinash singh

Both NGR and NGT are used to for restricting earth fault current. The standard practice is to have a single grounding in a system with same voltage. If we generate 11kV through the generator and there is no step up transformer before connecting the generator to the generator Circuit Breaker than we will have to use NGR and restrict current at 100A instead of restricting it at 10A as the relay at the feeder side will not be able to detect such small fault current as the relay is getting its input reading from a CT which might be above 1000/1A rating. The relay will not be able to sense small value current as low as 10A as it is quite a low value. So we need to consider NGR considering the sensitivity of relay and CT.
When there is a transformer between generator and generator circuit breaker than you can have the secondary of the transformer grounded and you will get the path for earth fault at feeder end through that grounded system. Now in this case you need not protect the feeder from the generator side and you only need to protect the generator now. So, you will keep the current because of earth fault as low as possible which enters the generator. In this case you can use an NGT and lower the earth fault current to 10A. The CT for sensing earth fault current will be connected at secondary i.e. LT side of transformer and as the voltage is low there, the current will be more and CT can easily sense that much current and the relay will trip the generator as soon as the fault occurs. The resistance will also be connected on LT side of transformer as we can connect low value resistor there and it will have a higher value resistance effect on the primary side of NGT which is HT side which is connected to the main neutral line of generator. Hope this answer helps.

Is This Answer Correct ?    9 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How can maintain our H.T. motors used in cement plant. please send me procedure.

5111


wat is d diffr btw shunt coil and trip coil in VCB?

2790


Type of motor stater detail and working detail

1622


I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.

1374


when measure the core loss of three phase distribution transformer or three phase reactor loss, one phase shown negative watt loss. why??

1943


What is sensitivity of a measurement?

1087


as a electrical student why should i hire you?

2451


WHY IL=IPH IN STAR AND WHY IPH=IL/1.732 IN DELTA? WHAT IS REASON BEHIND IT?

6278


What is the abbreviation of NGT panel

1995


with out colour codeing on conductor how can be find what is r,what is b,what is y phases.....

1911


What is the difference between shortcircuit current, rated current of cable & MCB with example? What will be the size of cable required for 5.5 KW motor (Full load current 10 Amps approx.), Starting current with DOL is 120 Amps. Aprrox. Short circuit current with LLLG fault is 2000 Amps Approx.

2021


Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.

2326


Sir, I m 3rd year student 4m DCE and want to do internship in siemens or l&t or any other mnc related to electrical engineering. please tell me the procedure 4 same and oblige me

1943


Define branch?

1050


how could we know the size of cable by physical view?

1579