How do understand by hart protocol?
Answer Posted / jigaranadkat
HART : Highway Addressable Remote Transducer
This is a communication protocol in which all information related to transmitter / instrument travels in the same pair of power loop of transmitter.
This information is transmitted by superimposing HART signal (AC) on 4-20mA DC signal. Hence HART DC value remains zero and it will not impact 4-20mA measurement.
The digital HART information is transmitted by two different signal 1200 Hz (Represented as 1) and 2200 Hz(Represents 0) in digital system.
Since transmitter are Highway Addressable, it is possible to configure transmitter remotely through a management system (e.g. AMS or PRM).
Hope this will help.
Regards,
Jigar Anadkat
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is solenoid valve? Where it is used?
How to measure the dust in chimney(spm)?
what is the electrical operation procedure for switching on 27.6MVA electric furnace.
Dear Friends, we are planning to design Power distribution and Fiber optic in the same cabinet.Like Front side Fiber optic and Rear side Power distribution.Is it any possibility of problem occurs like interference etc? Your answer is highly appreciate.
What should be the main consideration while starting the Rotating compressor when we dont know the cut in and the cut off pressure setting of the pressure switch
hi! i want to know about mpse exam.
what does it mean an active front end in vfd plz explain it briefly
Explain the burnout feature.
What is cut off relay? And why use in PLC and DCS?
what is insdustrial vibration.who it works. give atleast 2 types of insdustrial vibration
can we create an interrupt in plc through scada?
what is thermo coupler and how it works
Explain the use of hair spring in the pressure gauge.
I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?
how to work MIL contol valve posistioner ?