Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

i have 3, 75hp motors and 10, 15 hp motors....and to run this motors continously with a generator how much rating(kva) of generator will suiteble....?

Answer Posted / channa

1 HP = 746 WATTS
Your total load is 153.75 HP

153.75*746= 114.6975 KW

KVA = KW/P.F
=114.6975 / 0.95
= 120.7 KVA.
150 kva generator will be more than enough

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is tan delta & PPM in transformer? and whats its IS value?

2145


why Lightning arrestor are made by 2 seperate stack of inslutor but why cvt are in single stack of insulator.

1971


What is the meaning of C1, C61, C91 cable

3456


why sielent pole is used only in hydro generators and not in turbo generators

4177


How 48-relay (incomplete sequence) functions?

4091


What is the drawback of class b amplifier? How is this minimized?

1124


A double circuit with dog conductor 66KV Transmission line from wind farm evacuation to feeding substation having capacity of 25MW for transmission. Can same transmission network be considered for further expansion of Power & how much in MW. If we need to expand next 10-15 MW more will there any augmentation is required in transmission network? Kindly reply asap.

2190


why lightning arrestor are made in two stack of insulator but why not cvt

2067


When are the directional relays used?

1049


what is physical distance of isolator to VCB in 33/11kv sub stations

2131


How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?

1831


how many types control panel of a 132/33 kv substation

2642


What is the difference between single point and double point bonding. please kindly detail about bonding of cables.

2440


What is the necessary condition for stability.

1196


How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540

1095