i have 3, 75hp motors and 10, 15 hp motors....and to run this motors continously with a generator how much rating(kva) of generator will suiteble....?
Answer Posted / channa
1 HP = 746 WATTS
Your total load is 153.75 HP
153.75*746= 114.6975 KW
KVA = KW/P.F
=114.6975 / 0.95
= 120.7 KVA.
150 kva generator will be more than enough
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is tan delta & PPM in transformer? and whats its IS value?
why Lightning arrestor are made by 2 seperate stack of inslutor but why cvt are in single stack of insulator.
What is the meaning of C1, C61, C91 cable
why sielent pole is used only in hydro generators and not in turbo generators
How 48-relay (incomplete sequence) functions?
What is the drawback of class b amplifier? How is this minimized?
A double circuit with dog conductor 66KV Transmission line from wind farm evacuation to feeding substation having capacity of 25MW for transmission. Can same transmission network be considered for further expansion of Power & how much in MW. If we need to expand next 10-15 MW more will there any augmentation is required in transmission network? Kindly reply asap.
why lightning arrestor are made in two stack of insulator but why not cvt
When are the directional relays used?
what is physical distance of isolator to VCB in 33/11kv sub stations
How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?
how many types control panel of a 132/33 kv substation
What is the difference between single point and double point bonding. please kindly detail about bonding of cables.
What is the necessary condition for stability.
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540