A 200W,230V lamp is connected across 115V supply.The lamp will
draw power?
Answer Posted / tripti kumari
first we find the resistance of the lamp that is given by formula p=V*V/R
R=230*230/200=264.5 ohm
now current flow through the lamp when connected to the supply 115 V that is
I=V/R
I=115/264.5=0.435
now power draw by the lamp given by
p=V*I=115*0.435=50.025
so it is slightly more than 50 W.
| Is This Answer Correct ? | 95 Yes | 46 No |
Post New Answer View All Answers
Please help me regarding my one concern. - During earth pit testing we noticed that the Clean earth pit and dirty earth pit showing continuity (Resistance value - 5ohm) . I want to know that if both earth pit have separate location and there is not internal looping between PIT then why such continuity is showing on it . Because of this issue the field side all earthing point showing short. In PLC panel we are providing two types of earthing cable which is coming from separate earth pit (Clean and Dirty earth pit) because of earth PIT showing short our PLC is not complying spec . please help regarding this issues.
which pump used in STP
What is q factor?
What is the phase relationship between the primary and secondary voltages of a transformer?
which book to refer in electrical engineering for iocl exam & which book for general english.
anyone knows service engineer in chennai for EDM SPARKING MACHINE.CHMER PULSE CD 60 M.pL GIVE ANY CONTACT NOS
State uses of different types of stsrters with different capacities of motors as below: a. up to 5HP b. above 5hp to 10hp c. above 10hp to 20hp d. above 20hp
11000volt DG set carnt kaise banvay
What is George phenomena to start the synchronus machine?
Mr. mohh sahid m not satisfied for ur answer to the que weather the size of transformer increases or decreases withchange in fr for more detail go to the answer given by me
What will happened if the neutral of secondary of Xformer ( Star point) Note it's above KVA rated Xformer
What is meant by vector group
How is operate breaker failure scheme in substation
Good day everyone,currently in our premise we using 30kw slip ring motor with resistance bank which we use as forward and reverse at conveyor bar handling. So,my question is how do we calculate the resistance bank which is suit the motor. Kindly,assist me... thank you
how flow current in 220 kv line to line