why battery dc voltage become Half when we check with
respect to ground for example 120volts + and - terminals
and when we check + terminal with Earth thats 60volts why
60volts same result on 24Volts and with ground 12Volts only
expert answer that thanks
we can not ground the battery.
Answer Posted / k.prakashchandra
In case of bridge rectifier , the mid tap of the rectifier tr is earthed or two high resistances in series are connected across the charger out put terminals and the common point of the resistors is earthed . Hence the ground potential becomes (+ or -) zero
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is the difference between fault current ant short circuit current?
what is the prinsiple of dc motor and construction and working ,application of dc motor.
which stabilizer is better ? AVR, Servo Stabilizer, Static stabilizer etc & why explain it
What are the various kind of cables used for transmission?
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?
i need about 10 years of GATE solved papers in pdf format and even mock tests toooo
explain the types of drives
What range of speed can you get with the field control method of speed control of d.c. Shunt motor?
How is the gain affected by the introduction of feedback in a control system.
How i can calculate current of cable according to ares?
Why we use circular(Stepped) cross section in transformer core?
Assuming that a dedicated neutral earthing transformer is provided for each GT generator, when the two generators are running in parallel, has consideration been given that the earth fault current from one generator stator winding be split between the two neutral earthing transformers? If so, what adverse impact will this have on the operation of the 59N and 27TN devices?
Define end float in a motor?
What determines the thickness of the lamination or stamping?
WE ARE PLACE A NEW 75 KW MOTOR FOR JPF.IT IS CONNECTED IN M.C.C. WHEN WE ARE STARTING M.C.C.INCOMER IS TRIPPED.THEN WE ARE CONNECTED IN P.C.C WITH A MM30 RELAY PROTECTION THEN WE ARE STARTED MOTOR WILL RUN SMOOTHLY.