Is it possible to interlock between ACB & MCCB?
Answer Posted / g.pattabiraman
For positive, fail safe interlocking, between ACB and MCCB to prevent both getting ON at any given time,
use of UNDER VOLTAGE COIL, along with auxiliary switches of the breakers is needed
ACB under voltage coil in series with MCCB aux. N.C contact
and MCCB under volt coil in series with ACB aux. N.C contact will give this fail safe protection
Motor operation or manual operation are user choice
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
How to calculate MCB Breaking capacity.
Hello sir, pls send me hpcl technical test papers .i am. Appearing for the exam.
what is the question paper model for section engineer in RRB
How the capacitance og capacitor volatage transformer is decided?
How would you calculate power loss in a resistor?
How we can defined theecopper cable size if we know the aluminium cable size?
What is the mmf,rgt and ngt please brief completely
Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.
Why we use Electrical energy rather than any other type of energy, mostly? Explain behavior of open secondary CT and short circuited secondary PT in energized condition?
Parts of machine and their discription in details with suitable photo
Under wat condition statcom operates as an inductor for the transmission line?
If we connect a motor and generator together (I mean that the generator gives the motor electricity and the motor gives the generator movement) regardless the losses. Will the generator still generate and the motor still move?
What is the most important precaution in any experiment with d.c. Shunt motor?
how can we phase identification in a distribution line,how we recognise that which phase is coming for a house hold connection.help me............
How Diesel Generator start ?