why transformer ratings in kva?
Answer Posted / tarun aggarwal ymca
We know that Transformer rating may be expressed in kVA as well as Generator and Alternator rated in kVA
There are two type of losses in a transformer;
1. Copper Losses
2. Iron Losses or Core Losses or Insulation Losses
Copper losses ( I²R)depends on Current which passing through transformer winding while Iron Losses or Core Losses or Insulation Losses depends on Voltage.
So the Cu Losses depend on the rating current of the load so the load type will determine the powerfactor P.F , Thats why the rating of Transformer in kVA,Not in kW.
Designer doesn’t know the actual consumer power factor while manufacturing transformers and generators i.e. the P.F (Power factor) of Transformer and Generator/Alternator depends on the nature of connected load such as resistive load, capacitive load, and inductive load as Motors, etc.
But Motor has fixed Power factor, i.e. motor has defined power factor and the rating has been mentioned in KW on Motor nameplate data table. That’s why we are rated Motor in kW or HP (kilowatts/ Horsepower) instead of kVA.
In addition, Motor is a device which converts Electrical power into Mechanical power. In this case, the load is not electrical, but mechanical (Motor’s Output) and we take into the account only active power which has to be converted into mechanical load. Moreover, the motor power factor does not depend on the load and it works on any P.F because of its design.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
please describe the Transformer setting, Motor setting, I/C setting, Tie setting
Why in power plant projects we see DOL starting method used for motors upto 160 kW instead of star delta method
Sir, plz tell me how droop setting is done in parellel operation od DG set ? please give practical example ?
what is the use of piston rings in the engine used for a generator...........
What can you contribute to the progress of our Company as an employee if you are selected?
what is sevice settings for mccb?How can be it setted?
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???
how we arrange the hv side with delta connection in case 33/11kv of transformer.
what is the Earth Voltages in Power Plants, Sub-stations, Industries, Residential & Commercial Buildings.
Can anyone explain me about the RLC based Impulse high voltage generator and how to and operation of Series resonant High voltage reactor...?
How do we calculate the Out put voltage of generator, after the excitation is being given?
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
determine two methods to find loose connection in operational electrical system?
How may I enrol or get admission to your program?
what is the advantage of connecting capacitors in delta than in star?