15hp,380v,31amp,3-ph submersible motor run at 250v what is
The temperature rise of submersible motor
Answer Posted / shubha_ee
If motor is fed from Delta connected supply.....
P=15hp = 11.19kW
so P per phase = 11.19/3 = 3.73kW..
pf = 11190/(1.732*380*31) = 0.55(lag)
then Vp=VL = 380V..
and
Ip=IL/1.732 = 31/1.732 = 17.9Amp..
So, R per phase = (380)^2/P = (380)^2/3730 = 38.71 ohm..
so, Heat dissipation for 1sec due to I^2R loss,
H1 = (17.9)^2*38.71*1 = 12403.07 Joules...
Now, if the VL=250V = Vp then IL= 11190/(1.732*250*0.55) = 46.98Amp...
so, Ip=46.98/1.732 = 27.12Amp...
So, Heat dissipation due to I^2R loss for 1sec ,
H2 = (27.12)^2*38.71*1 = 28470.98 Joules...
Now, increase in heat dissipation = (H2 - H1) = 16067.91 Joules
so, increase in temperature is 8.46 deg Celcius.....(as 1degC = 1899.1005 Joules)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Grid fault level [KA]?
Sir, I m 3rd year student 4m DCE and want to do internship in siemens or l&t or any other mnc related to electrical engineering. please tell me the procedure 4 same and oblige me
how is the testing of an REF relay? what are the test REF circuit having?
how to generator maintenance (A Check, B check,Etc)
what is the function of impulse relay
If VFD is On but no starting commond on it. so how many outpout voltages of VFD
how we design a pannel to start 10HP motor with the help of star delta starter?
Generation of voltage for each phase are same of a turbogenerator.Although the short circuit current flow when two phase of turbogenerator are shorted(where current can't flow without potential difference),why?
What type of a DC motor would you use for a lift?
What is the difference between Delta & Wye windings?
If SFU is Switch Fuse Unit, What is the expansion for FSHF in Electrical Engineering?
What are the application of filter?
How to decide and select the different earthing wire size for the different types of earthing
what is lrs tank water resistance.
A TRANSFORMER 440/400V,DELTA/STAR CONNECTED.THE NEUTRAL CONNECTED WITH GROUND CABLE THAT IS DIRECTLY CONNECTED TO THE PANEL,FROM PANEL IT IS CONNECTED EARTH PIT.IS IT RIGHT? IF IT IS RIGHT LEAKAGE CURRENT AFFECTED.SECONDATY IS PROTECTED WITH EARTH LEAKAGE RELAY.