In D O l starter motor starts as a star connected ,then in star delta starter also motor initially starts as star how come star delta is preferred from dol

Answer Posted / jayant mistri

It is not correct that in DOL starter, motor starts in star connection. But motor starts with Line voltage i.e 415 volts P-P in our country. It is the motor which is connected in star or delta connection from terminal box or in the motor winding.If motor is connected in star connection,each winding (R,Y and B phase) of motor, get phase voltage i.e. 230 volts (motor gives less power i.e. motor power /1.73). and if motor is connected in delta connection,each winding (R,Y and B phase) of motor, get line voltage i.e. 415 volts.motor gives rated power.

In star delta starter, motor start in star and changes to delta connection after time delay. In star connection motor draws less current as each winding gets 230 volts and when it goes to delta connection each winding get line voltage. thus star/ delta starter starts motor in reduced voltage so that motor draw less starting current. This starting is called reduced voltage starting.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What will be the current drawn by HT motor, if low voltage is applied.. any formula to calculate the LT amps of HT motor.?

1018


is all the servo motors having brake?please specify which servo motors having brake for stop on position and which are not.

1325


wat is d diffr btw shunt coil and trip coil in VCB?

2357


1.dg on load alarm/stop alarm... 2.dg on load. piu alarm alarm kaise chek krte hai

1394


where lt & ht capacitor used

1767






WHAT IS AIR GAP VALUE IN MM FOR A 11KV BUSHING OF 11KV/440V DISTRIBUTION TRANSFORMER. AND AIR GAP VALUE OF 25 KV BUSHING OF AT TRANSFORMER OF 25 KV TRACTION. WHAT IS THE CALCULATION FOR THE AIR GAP PERMITTED FOR BUSHINGS AT DIFFERENT VOLTAGES.

3052


how much flux density of CRNO core

2365


Define rise time.

616


How many devices can be connected in one zone of FACP

1800


i have seen one 8.4 MW synchronous motor in a plant located in bellary it is fixed with brushless rotary rectifier ,anybody can explain its start up principle

1513


reason of diode failure in alternator

1409


what is the difference b/w UHVDC and HVDC(LIGHT)?

4865


What is the formulae of Megger value for a A.C.Motor

2299


what is the basic construction diffrance between servo motor ans sqiralcage induction motor

2018


what you have to see after one week or month from the day of installation of transformer ?

1243