What the capacitor Current formula?, For 1 KVAr how amps
its required? for using the KVAr for boosting the PF Design
Calculation.( Eg: for 30 KVAr required how many KW?)
Answer Posted / kalanidhi
Current calculation for 200 kvar capacitor
CAPACITOR VOLTAGE CALCULATION
#System Voltage (MV) : 433V (WITH +- 5%)
#Voltage drop across (Maximum) : 433 x -5% = 21.65V
Capacitors working : 411.35 Volts.
CAPACITOR CURRENT CALCULATION
KVAR Calculation at 433 Volts.
KVAR 433 Volt (433)2
= ------------ 200KVAR
(411.35)2
187489
= ----------- 200 KVAR
169208
= 1.1 x 200 KVAR = 221.59
= 221.59 KVAR
Current for 221.56 KVAR at 433 V = 221.59
------------------------ x 1000
433 x 1.732 x 0.6
= 492 Amps.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
list the type of vfd? wich is sutable for heating kiln?
What is Harmonics how it is produced and what is the method to control the same
what is the internal working of star delta starter
Name the types of motors used in vacuum cleaners, phonographic appliances, vending machines,refrigerators, rolling mills, lathes, power factor improvement and cranes.
how to do the ductor test?
can any one provide me a connection wiring diagram for a DG set control panel along with BOM?
what is the sludge current
how can we find thae value of capacitor for single phase motor. what is difference between starting capacitor and running capacitor.
On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?
What is the necessary and sufficient condition for stability.
how many types are their in switchyard or substation(like D,I TYPE), what is differant between them
before synchronizing an alternator,power factor is leading ,why?
How to determine stage of Automatic Power factor controlling Relay(Apfcr)?
How to synchoronize the generator (with gcb,GT) to grid????? ????? from Grid iam getting power (rated 400kv/20kv) through GT and its goes to UAT.,,ST.,, now my generator(rated 20kv ) ready.,, now iam closing my GCB.,, in GT iam suddenly giving 20kv on that Gt.,, what will happend
what will be the maximum winding temperature of 6.6kv HT motor 450kw, Full load current 49A. 50Hz Frequency.