Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How a Flow Transmitter Works?

Answer Posted / rijo dennis

A Flow transmitter will produce 4-20mA as its output. According to the differential pressure applied to the diaphragm of the D.P it will produce electrical signal. In the cause of the flow the out put current will be in the square root proportional mode, i.e
input= 0% then output= 0% 4.00 mA
input= 25% then output= 50% 12.00 mA
input= 50% then output= 70.71% 15.31 mA
input= 75% then output= 86.60% 17.85 mA
input=100% then output= 100% 20.00 mA

For a level transmitter it will be operated in linear mode,i.e,
input= 0% then output= 0% 4 mA
input= 25% then output= 25% 8 mA
input= 50% then output= 50% 12 mA
input= 75% then output= 75% 16 mA
input=100% then output= 100% 20 mA

The same DP(Differential pressure) Transmitter can also used for both flow and level,but the one and only change in the mode of operation. flow is proportional to the
square root of the DP,but floe is directly proportional.

Is This Answer Correct ?    10 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Tell about your IFFCO plant visit.

2077


why we are using magnet for calibration of gas detector?

2251


WHAT IS MEANT BY PROJECT MANAGEMENT STRATEGIES IN INSTRUMENTATION?

3551


the pump holds on run indication into the dcs and filed local control panel remote push button condition operaton wrong like when the push button pushing conditions the pump is off and the push button release condition the pump is on totally opposite condition . And control room inside give the stop command into dcs just 1secon relay engage and again normal condition. How can I slove

1699


Instrument QA/Qc what is the project quality plan?conduit inspection RFI. which documents attache with package?

10849


line up procedure for dp type flow transmitter?

1902


Why plc require in analog input 4-20amp & 0-10 volt?

1140


what is piezoelectric transducer?give an example in power plant n state its principle?

2595


What should be the main consideration while starting the Rotating compressor when we dont know the cut in and the cut off pressure setting of the pressure switch

2212


Explain how thw analog to digital converter works with the circuit diagram

2671


There are many type of control cable like pair,core,tried, What are defination each one

2154


components of control circuit belongs to control valve

1659


Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75 The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is: WARNING: Could not connect to equalize destination. (7001) Retrying. Number of retries = 0/1 ERROR: LdXopsLoadMain: connect error 10060 ERROR: Processing terminated due to connection error. (7002) Equalization end with errors. STN0149 ---- ERROR = 2 WARNING = 1 ---- Background: >Updated the ExaOPC software on the STN from 3.60 to 3.75 >STN operating system is Windows Server 2008 R2 >HIS operating system is Windows Server 2016 Stanard Solutions attempted include: >Ensuring all IP addresses are correct and all networked devices can be pinged. >The ability to ping a device using its host name from another device ( from HIS) >Ensure both devices firewalls are disabled. >The antivirus installed on the STN is disabled. >Ensuring both devices are within the same workgroup. >Added both devices to each other's Host and LMHost files. >Running IT Security tool after changing any administrative settings.

2195


where proximity sensor installed on tank in loading arm application

2268


where uses EXe /EXd/Exo/Exn/Exp/Exq/EXia

9925