Answer Posted / carl_ellis

What is passive connection of instrument in different type of I/O module?

What is passive connection of instrument in different type of I/O module?

The output of a field instrument or analyzer that makes a measurement and provides a conditioned, high level signal like 4-20mA is characterized as either active or passive.

An active output is powered internally by the instrument. These are 3 or 4 wire instruments with a separate power wire or wires.

A passive output requires a DC power supply in series with its output in order to excite or power the output. This done to
- limit field wiring to 2 wires
- reduce the likelihood of a ground loop due to difference in ground potential between the field instrument and the receiver.

So, a connection of a passive (2 wire, loop powered) device has to include connections to a DC power supply, observing correct polarity at the field device and the receiver's analog input.

Carl Ellis
Measure First

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?

1824


Can anyone send most commonley asked Instrumentation questions and answers in cement industry please?

1643


where proximity sensor installed on tank in loading arm application

1601


give me the formula for analog to digital converter and also d to a converter

2473


Sir , i have completed my M.Sc In Instrumentation and presently working in Maintenance department 3 yrs Exp , is there is any possible for work in offshore ..

1491






how can use ram

1569


dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.

1508


how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.

1959


please tell me what is a light up procedure of Cfbc boiler and what it's axuillaries of cfbc boiler?

8296


HOW TO SOLVE PROBLEM WITH ENRAF LEVEL TRANSMITTER 854 ATG THAT PASSWARD DO NOT Exist INTO TRANSMITTER TO ADJUST LEVEL WITH PORTABLE PET 847, WRITTEN WRONG PASSWORD , I AM SURE THAT DEFAULT PASSWARD (W2=ENRAF2) IS THIS TRANSMITTER NEED TO REPLACE SOFTWARE AND HOW?

3115


We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.

1233


In turbine, what does term CDP, NI, NH, HSSOC, means

2288


How works weighfeeders in cement industry? what is the working principle?

1629


If a warning lamp will operate with the ground circuit is bypassed with a jumper wire to ground, what should you check?

1716


, Instrument Index, P&ID review, I/O schedule, datasheet, DCS / Analyzers specifications, loop diagrams, hook-up drawings.

7704