sir, in a industry present pf is 0.54 pf 25hp power is there
its want improve 0.9 pf. which suitable capacity capacitor is suitable please inform me.
Answer Posted / vishwas g. darne
You can use the the degree of P. F. Correction your load is
25 h.p. i.e. 25*746=18650-18.65kW present p.f.is .54 require p.f. is 0.9 degree of p.f. is 1.075 required kVAR per kW is 1.075 Therefore capacitor rating should be 1.075*18.65=20.04kVAR.