Can 2 transmitters be connected to Integral orifice meter taps? Does an integral orifice comes with 2 set of taps?
Answer Posted / carl_ellis
Integral orifice plate assemblies are either designed to install as part of the process piping with flange mounts for a manifold valve, or for direct mounting to the process heads of a DP transmitter so that no transmitter piping is required. They're designed primarily for low flows.
Although intended for direct mounting to a manifold valve or process heads, optional fittings are available for high temperature applications that move the transmitter away from the integral orifice assembly. Presumably, fittings for dual transmitters could be fabricated as well.
Commercial orifice flange unions have a single tap on each flange. It would be possible to tap a 2nd DP transmitter into the piping for those taps.
Dual or even triple transmitters on a single flow element and set of taps are sometimes referred to as 'stacked' transmitters. There are commercial adapters for close coupling dual DPs with a special manifold valve from vendors like Century Valve. This has a long history of useage to cover a wide flow range with multiple DP transmitters, each of has a relatively low or limited turndown.
An SIS safety calculation has to account for a single-point-of-failure with a single set of taps.
There's always the possibility of a corporate engineering policy discouraging or forbidding dual DP transmitters on a single flow element and set of taps.
Carl Ellis
Measure First
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?
how many types of preheaters are in cement industry & what r they can any body explain?
sir, i preparing hpcl,ongc,barc,hal exams(instrumentation engg)pls send a placement papers
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
what is the procedure of belt scale calibration?
Name different parts of a pressure gauge.
how to convert cubic metre per hour to newton cubic metre per hour
Draw a great bridge circuit.
Why is it necessary to use compensation leg to measure the liquid level in a closed or pressurized tank?
PT RTD Range: -200 to 500 degree celsius If I configured in DCS Lower range and Upper range . In face plate it shows red colour due to overa range how was the characteristics look If the temperature is more than operating range. how was the characteristics look . whether its in Resistance vs Temperature curve is Linear or Non linear
protection relay watchdog contact operation?
what is the PC interface and software for connection to ABB logic module “ LM011-CE18RAC “ ( for Programming ) ??
give me the formula for analog to digital converter and also d to a converter
Hi, Is there any smart plant instrumentation design training institute in Bangalore?
plz send me general of ongc