Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

When we give supply to a transformer 11 kv and we get 415v
from it, so when we give supply to same transformer 415v on
ht side what we get?
and
When we gives supply to any transformer to L.T. side 415v or
220v What supply is on H.T. side?

Answer Posted / ramakrishna

When we give a supply of 11 KV on HT side and we get 415 V from LT side, the transformation ratio is 26.5(11000/415). 
So,
1) If you give a supply of 415 V on HT side of the same transformer then you will get 15.6 V(415/26.5) on LT side.

2) If you give a supply of 415 V on LT side of the same Transformer then you will get 11KV on HT side.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1996


Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?

2557


how does the rotating m.m.f is produced in the 3-phase induction motor and how the poles are created in 3-phase induction motor ?

2650


What do you mean by a phase angel of instrument transformer?

1122


why the difference arise between HT reading & LT reading (submeters fixed in complexes, apartments etc)if the power factos exceed from 0.9 to 1 can the ht meter reads fast?

2975


What is an Air COmpressor

2250


there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit

1935


What is the estimated total hydropower potential of india?

1144


A jet of fluid strikes a plate What was the force required to counter it?

1880


What is difference between mcb and mccb.

1158


Define demand factor?

1130


What are motor generator sets and explain the different ways the motor generator set can be used ?

1175


how to choose cable size with respect to load? how to convert cable size in mm2 to sq.mm?

6012


My question is whether bellow formula is correct to find bus size for 46kA for 0.5 second & what is RT in bellow formula. formula to calculate the size of busbar to withstand the thermal stresses due to currents with duration of 0.2 sec to 5 sec. Sp = RT( I x I x t) / K Where Sp – is the cross sectional area of bus bar in millimeters. I -    is the value of AC fault current. t -    is the operating time of disconnecting device in seconds. K –  is the factor depending on the material of the conductor, insulation and initial and final temperature. Value of ‘k’ for copper is 143.

1890


What are the advantages and disadvantages of the ac motors?

1132