WE Know that different supply voltage of solenoid valve like 24,110,220 etc..how we check the solenoid supply is 24v or 220 NOTE: No specification at device.
Answer Posted / carl_ellis
1) Put a voltmeter on the solenoid terminals and see what the control signal supply voltage is. It could be AC or DC.
2) Go back to the control signal source and trace the wires until it becomes apparent what the control signal voltage is.
3) Dig out the electrical drawings and see what control signal the circuit was designed for.
4) Measuring winding resistance is dicey (not terribly reliable) because the wattage ratings on solenoid coils covers a range of about 3:1, so the difference between a DC coil and an AC coil, or between a 6 or 9 watt coil is overlapped by different wattage coils for different services.
Carl Ellis
Measure First
| Is This Answer Correct ? | 1 Yes | 3 No |
Post New Answer View All Answers
If fire would be inside the plant which fire detector is to detected the fire.
Why ac supply load cell is used? Can we use the dc supply load cell?
PLEASE PROVIDE SAMPLES OF CHEVRON SKILL TESTS
why Fahrenheit unit of moistur analyzer transmitter
Why we are using reverse action in displacer types level transmitters on some Vessels?
how we are selecting instuments by differentiating certain instruments in 4 to 20 ma range and certain in 1 to 5 v dc
if in a level tx height is given, how u calculate the ranges of the tx?
Draw a wheatstone bridge circuit showing supply, meter and 3 wire RTD connection
How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.
What is the formula of vabration sesore. i mean how to covert mils to volt plz share if any body knows very argent : my mai is merajalam143545@yahoo.com
What should be the main consideration while starting the Rotating compressor when we dont know the cut in and the cut off pressure setting of the pressure switch
Positioner usage.
What is difference between “Fault Tolerant” & “Fault avoidance” PLC? Application where these system s are used?
If a control valve is hunting means means if we are giving 50% to the cv, the cv will open at 51% then slowly slwoly it will reaches 49% , so what to do for solve this problem. The cv is double acting and mounted for anti surge operation, it having 4 nos. volume booster, one sov, one positioner, etc..?
why I need valve guard and whats different between guard and positioner ??