HOW CAN I CONNECT ROSEMOUNT 3300 LEVEL TRANSMITTER TO
Allen-Bradley SLC500
Answer Posted / carl_ellis
The 3300 is a 2 wire, loop powered guided wave radar level instrument. So it needs 16-42Vdc for power; typically a 24Vdc power supply is used. Copper wire cable, shielded, twisted pair is used. If the radar is in a hazardous area, then either the installation is designed for explosion proofing or Intrinsic Safety (which uses a barrier or I/S isolator).
The SLC500 PLC needs a 4-20mA current analog input card. Usually the instrument power supply is separate from the rack power supply.
The wiring is shown in the manual, but it is traditional 2 wire loop powered wiring.
Carl Ellis
Measure First
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
Where Can i take a SPI INtools training in Mumbai? In Rolta India Ltd to whom I should approach regarding of SPI INtools Training?
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
What is wet leg condition and why is it used?
what is temperature compensation?
How can a d.p. Transmitter be calibrated?
How to calibrate capillary type level transmitter
Can u tell me the principle of the tc,rtd,level switch,pressure switch ,transmitter(pr flow level temp.),vibration...plz
How do bending tubing provide better measurement than using tubing fittings such as elbows?
defination of radial vibration?
I need to know steps to Calibration Valve Guard......
Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .
Which language of programing is popular? how can i learn it ?
Can anybody tell me which type of question are asked in the interview for the FORMULATION(Pharma) as a instrumentation engineer, & question in building managment system.
What is the difference bitween control net scaner and device net scaner
Why plc require in analog input 4-20amp & 0-10 volt?