how we are desining 63.5 ohm resistor for NGR of alternator?
Answer Posted / vg
to limit the earth fault current generator/Alternator NGR design. ex. for 11KV generator Earth Fault Current to be limit on 100 Amp.
V=I*R
R=V/I
so I=11000/1.732*100=63.5Ohms.
11KV generator NGR 63.5 amps for 100 Amp fault current.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
i want to run 11kv star connected motor in 6.6kv with delta connected throught inverter, is it possible?
what kelvin's law ?
why output is out of phase in case of common emitter?
hi friends ,iam working as genset AVR service engineer in electrical field from past 2 yrs throughout india . i plan to shift in some other job without travelling in same field because i con't travel,i dont know what i do for that so please guide me what job is suited for me,how i can serch the job please anybody helpme iam totally confused