Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to select a D.G set for calculated load of 110kW..?

Answer Posted / sanjay vishwakarma

CONSIDERING 110kW AS INDUCTIVE OR MOTOR LOAD
Ir (RUNNING CURRENT) WILL BE 110*1000/1.732*415*0.8
Ir = 191.3 AMPS

CONSIDERING MOTOR STARTER AS STAR-DELTA,
Is (STARTING CURRENT) = 3 TIMES OF Ir (RUNNING CURRENT)
Is = 3 * 191.3 = 574 AMPS

IF MOTOR WILL START ON NO-LOAD CONDITION, THEN STARTING
CURRENT WILL ALWAYS BE LESS THAN 574 AMPS

DG SET RATING SUITABLE TO START 110kW MOTOR LOAD IS 365KVA

365KVA DG SET AT 0.8 PF WILL DELIVER 507 AMPS. SINCE DG SET
ENGINES ARE PRIME RATED I.E. AFTER EVERY 12 HRS, DG SET CAN
BE RUN ON 110% LOADING FOR 1 HOUR.

SO, 110% OF 507 = 557.7 AMPS,

HENCE, 365KVA DG SET IS SUITABLE TO START A MOTOR
(INDUCTIVE) LOAD OF 110kW


WILL BE IF MOTOR WILL BE STARTED ON NO-LOADSINCE MOTOR
SHALL START ON NO-LOAD

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

state the working of discharge lamp?

2043


What is creepage distance..... what will be the value for different voltage level

1986


How to calculate ant test the burden of Current transformer

2456


when we decide to use soft starter drive or vfd drive in mcc to operate apump?

1986


hello everybody. what does an abnormal stator winding impedance or dc resistance show? thanx

1922


I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?

3816


What is excitation in case of dc motor?

1170


what are the problems that generally occur in power flows??

3257


How short circuit MVA(Fault MVA) in a power system calculated for calculating number of earth plates ?

2305


give me atleast four differences between circuit and network

2182


What about electrical Units. discrive in detail

2098


Explain the operation of variable frequency transformer?

1146


What is power relay?

1246


Why Transformer Neutral having one earth pit ( more earth electrode resistance) whereas body have many earth pit ( less earth electrode resistance)?

4334


What do you mean by Stimulastion Test in Diesel Genarator / Why & when it's conducted ?

1658