How to select a D.G set for calculated load of 110kW..?
Answer Posted / sanjay vishwakarma
CONSIDERING 110kW AS INDUCTIVE OR MOTOR LOAD
Ir (RUNNING CURRENT) WILL BE 110*1000/1.732*415*0.8
Ir = 191.3 AMPS
CONSIDERING MOTOR STARTER AS STAR-DELTA,
Is (STARTING CURRENT) = 3 TIMES OF Ir (RUNNING CURRENT)
Is = 3 * 191.3 = 574 AMPS
IF MOTOR WILL START ON NO-LOAD CONDITION, THEN STARTING
CURRENT WILL ALWAYS BE LESS THAN 574 AMPS
DG SET RATING SUITABLE TO START 110kW MOTOR LOAD IS 365KVA
365KVA DG SET AT 0.8 PF WILL DELIVER 507 AMPS. SINCE DG SET
ENGINES ARE PRIME RATED I.E. AFTER EVERY 12 HRS, DG SET CAN
BE RUN ON 110% LOADING FOR 1 HOUR.
SO, 110% OF 507 = 557.7 AMPS,
HENCE, 365KVA DG SET IS SUITABLE TO START A MOTOR
(INDUCTIVE) LOAD OF 110kW
WILL BE IF MOTOR WILL BE STARTED ON NO-LOADSINCE MOTOR
SHALL START ON NO-LOAD
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
why we are using earth pit in sub stations.?
1.dg on load alarm/stop alarm... 2.dg on load. piu alarm alarm kaise chek krte hai
If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?
what happens if dc supply is given and the remedies for it.
why dc is used in control circuit for mv & hv switchgear instead of ac
what is differnce btwen lll and lllg faults
Who are the manufactures those manufacturing 3Cx2.5sqmm FRLS cables. I heard about FRLS technology adopted only in wires useful for wirings
What are the effects of adding a zero to a system?
Please, if 1kw is equal to 1.25kva; how then do I know how many kva in 7.5kw?
On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?
How would you calculate power loss in a resistor?
3 phase induction motor connection star or delta while using ac drive motor is .75 to 5.5 kw
How to calculate mf when meter equipment and meter are connected
If you have an earth with pilecap then your resistance is really low. why and how?
What the formula for calculating no.of earthings & size of earth strip for 100mX90m shop.