1)why we are using mostly Ultrasonic Flow meters to measure
flow, rather than Radar waves?
2)why we are using Ultrasonic waves and Radar waves to
measure the Level?
Answer Posted / carl_ellis
1)why we are using mostly Ultrasonic Flow meters to measure
flow, rather than Radar waves? 2)why we are using Ultrasonic
waves and Radar waves to measure the Level?
Most fluids will 'conduct' ultrasonic energy. Conduction
is necessary because the energy needs to originate in a
transmitter transducer, pass through the liquid and be
received by a receiver transducer. The movement of the
fluid changes the sonic velocity of the energy, which is
measured to then calculate a flow rate.
Many fluids either reflect the radar frequency signal or
absorb the signal so that there is not enough energy left to
measure.
Radar frequencies reflect when a radar signal encounters a
dielectric difference. So radar easily passes through air,
with a low dielectric constant, but reflects back from
water, which has a high dielectric. So radar is useful for
level detection with liquids or solids that have a
dielectric higher than the minimum required to reflect
energy back to the transducer.
Ultrasonic energy reflects from most liquids and solids so
it can be used for level measurement.
Carl Ellis
Measure First
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
1. what is modbus cable? 2. what kind of communication we are using for the interface of DCS, ESD and Third party cabinets? 3. What is serial communication and peer to peer communication?
how to calibrate and troubleshooting of leveltroll?
What is the use of temperature compensation?
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
Explain the working of an electronic level troll.
In VVVF DRIVES VOLTAGE IS ALSO VARY WITH THE FREQUENCY. HOW? WHAT IS THE DIRECT FORMULA RELATING THESE TWO.
how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line
on interface level transmitter model(RTG3302-EMERSON) What is threshold valve how can we select correct threshold value T1,T2,T3,T4 When interface water & hydro carbon
can we copy the software from a transmitter using hht(hart 275) ?
How to Calibrate Ultrasonic Level Transmitter in field
NPN transistor, SCR, Zener diode, LED, Varactor diode, Vortex meter, RTD, Resistor, Crystal
what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.
how many pulses are required by a ac induction servo motor of 4 poles with 50 Hz frequency to rotate by 1 degree?
How to Calibrate Level Troll in field
What is the reason PT speed not incresed in gas turbine?