Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the difference between 5P20 class CT , PS Class CT
and 5P10 class CT??

Answer Posted / er.k.k.murty

K K. MURTY
--
5P10 & 5P20 Class CTs: They are generally used for Over
current (Instantaneous and IDMT relays) and E/F protection
of Feeders, Transformers etc.
(i) 5 signifies the % limit of composite error.
(ii) P signifies the Protection core,
(iii) 10, 20 signify the quantum of fault current as
multiple of the rated current or ALF(Accuracy Limit Factor)
up to which the CT shall have the defined percentage of
composite error i.e. ± 5%. During fault condition the fault
current is many times the rated current. Standard Accuracy
Limit factors as per IS: 2705 and IEC60044-1 are 5, 10, 15,
20 & 30.

Accuracy limit factor is inversely proportional to the rated
VA burden i.e. if the connected VA burden is lower than the
rated one, the limit of accuracy shall be maintained beyond
the declared one.
The formula for actual ALF;
ALF(ACT)= ALF(RTD) x {Sin+Sn(Rated Burden)}/{ Sin+Sa (Actual
Burden)}.
Example:- Calculate actual Accuracy limit factor if
secondary burden is reduced to 1/3rd, if CT rated as 200/5
A,5P10,15VA and Rct =0.15&#937;?
ALF Rated=10(From CT data 5P10),
Sin (Burden due to internal resistance of the CT) =
(5A)squre x 0.15=25 x 0.15=3.75VA,
Sn (Rated burden) = 15VA (From CT data), Sa(Actual Burden) =
15/3= 5VA,
ALF(ACT) = ALF(RTD) x {Sin+Sn(Rated Burden)}/{ Sin+Sa(Actual
Burden)}

ALF(ACT) = 10x (3.75+15)/(3.75+5) = 10x18.75/8.75 = 21.42
It is clear from the above example that the ALF increases if
the connected actual burden is lower than the rated one. The
CT in this condition shall maintain accuracy up to fault
current of 21.42 times of rated current as against 10 times
the rated current and shall not saturate till then.
PS Class CTs: Though abbreviation PS is not elaborated
anywhere, however it may be called as “Protection Special
Class” CT core. This core is used particularly where current
balance is precisely required to be maintained. In
Differential protection, balance is the prime requirement
between secondary currents of associated CTs of either side
of the equipments. Differential and restricted E/F
Protection of Transformers and Overall Differential
Protection of Generators need such CTS.
The 5P10P or 5P20 class CTs cannot match the Characteristic
as that of PS class. The core of PS class is such that very
high current is needed for saturation of the core. Knee
point voltage of the CT is of valid importance. The
developed voltage across the relay terminals should be lower
than the Knee point Voltage of the CTs.
From: Er.K.K.Murty, B.E.(Hons)Electrical,FIE.
Retd.Chief Engineer(Testing & Commnu),M.P.State Electricity
Board.
Jabalpur.
Email ID:kkmurty05@yahoo.com

Is This Answer Correct ?    81 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

On what basis the the size of Lightning arrester for buildings are selected ?

1661


how can we change the polarity of Alternating current rapidly? how frequency of ac can be controlled and changed easily?

2023


what is the electrical?

2117


the site measured knee point voltage of protection class CTs should be greater than rated knee point voltage? what about meetering class CTs. Should it be below the rated knee point voltage?

2291


what is the usage of microcontroller in the panel board?

2086


Testing procedure of DG alternator stability test

1572


What is the one main difference between ups & inverter ? And electrical engineering & electronics engineering ?

1146


Which type of a.c motor is used in the fan (ceiling fan, exhaust fan, pedestal fan, bracket fan etc) which are find in the houses ?

1031


What is difference between Sample test and Routine test in safety standard?

1945


What happened when voltage will half value of current ...

1620


I NEED RRB APTITUDE QUESTIONS AND MODEL PAPER,PLEASE SEND MY E-MAIL joo28_eee@yahoo.co.in

1928


how dose servo motor works

1924


diff. between tension mode & speed mode

2342


Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?

1965


why different series of vfds (like allenbradley)are used in industry ?

2308