I have a orifice installed in plant which is design for
0~100 inH2O for 0~80MMSCFD, now due to process change the
maximum flow is change to 120 MMSCFD so for this new
process value what will be the DP across orifice.
Answer Posted / carl_ellis
100 in H2O = 80 MMSCFD
x = 120 MMSCFD
Maximum flow rate is the square root of the normalized
percentage of the maximum DP (at the maximum flow rate)
The maximum flow rate increases 150% of the original max
flow rate:
120/80 = 1.50, so 120 MMSCFD is 150% of 80 MMSCFD, or a 50%
increase in maximum flow rate
To calculate the corresponding DP at a max flow rate 150%
higher than the original, where X = DP
sq rt of X = 1.50 (square root of normalized percentage of DP)
X = 1.50^2 = 2.25
2.25 = 225% (work in normalized percentage)
225% of 100 inH2O = 225 in H2O at a max flow rate of 120 MMSCFD
Carl Ellis
Measure First
| Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
Isometric drawings are generated during _________________ phase of a project
In dcs panel we are using diff type of modules ?what is module ? what is the use of modules ?diff type of module?
PLEASE PROVIDE SAMPLES OF CHEVRON SKILL TESTS
Why even multiple power supplu r used in instrumentation system?
find the kp ki kd from the transper function G(S)=29.44s+04707/1.5349s2+s
Sir,I am going to sit for IOCL written test exam. recently.Can anyone tell me the name of 'Objective type Question Book on Instrumentation Engineering ' which will help me. Pl. mail to bidyut_71@rediffmail.com / bidyut.saha2008@indiatimes.com / bidyut.saha09@yahoo.in
can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?
how to relay switch sense the fault?
, Instrument Index, P&ID review, I/O schedule, datasheet, DCS / Analyzers specifications, loop diagrams, hook-up drawings.
why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V
Which type of diagphram use in costic line,DM water line,natural gas line,oil line?
What is solenoid valve? Where it is used?
We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.
How to calibrate smoke Dectector
1. what is modbus cable? 2. what kind of communication we are using for the interface of DCS, ESD and Third party cabinets? 3. What is serial communication and peer to peer communication?