Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

IN OLTC we observed "OUT OF STEP" Alarm, we have two
different transformer, when both are in parallel this type
of alarm observed. what's the meaning of this alarm and why
it occurs???

Answer Posted / nasseem

Out of step means that the Two transformers at different tap.
i.e. TR-1 at tap n and TR-2 at tap n+1 or n-1.
And as you know the two transformers should have same tap
"if the two transformers have same tap size i.e 1.25% for
example" when it operated in parallel to prevent the
circulation current between the two transformers.

So it seems in your case if we assume TR-1 is master and
TR-2 is follower TR-1 change its tap position while TR-2
still at it is original tap.

Is This Answer Correct ?    13 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

i have done diploma and btech in EE and live in Chandigarh so kindly help me how can i make my competency certificate in my area.

2216


if the number of poles generated in stator and rotor side of an induction motor are different then what will happen and why?

1884


how do you test tachos and servos

2121


Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output

1840


is there any device that works properly accept relay, it may be fuse but if i want fuse of 33kv 300 amp it is avaliable, pls give me details

1996


why 3 phase is converted into 2 phase using electronics circuit why not 2 phases are diresctly putted from the 3 phase transformer??

2187


can we install HT panel & LT panel side by side or how much clearance is required ?

1594


what is rating boiler

1993


why different series of vfds (like allenbradley)are used in industry ?

2301


We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?

2150


what is the current density of copper & alluminium.

2063


How test for Ddo vector group test condition?

2468


what is doid

2816


where does 22kv line starts

3097


Why water bubbles when D.C. Current is passed through it? Why not when A.C. Current is passed?

2149