If a 1.5V,3W torch light bulb is connected in series with a
15HP/11.19KW,230V single phase motor and the combination is
connected against a 230V supply and switched on than what
will happen keeping all other parameters as it should be
A)the bulb will glow normally B)the bulb will not glow C)the
bulb will glow with extra brightness D)the bulb will burn
out and if a fuse is connected to the above circuit will
something happen to the fuse and what about the single phase
motor will it be affected?
Please explain with derivation
Answer Posted / azam
Hay raj you are wrong man 11.19kw moter draws less than 20Amps
P=VICOSØ for single phase motor where V=230v and if we assume cosØ=0.85 then current drawn by motor is
I=P/VcosØ=11.19*1000watts/230v*0.85=57.23amps
And kndeed bulb. Cnnected in series will blow up like fuse wire due to 3 to 8 times starting current passing througt bulb.as bulb operating volage and ampacity is low.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the loss of transformer of 220kv/11kv, 63/80 MVA and 18.05% impedance
WHAT IS THE WORKING PRINCIPLE OF A GENERATER.how is a GTG (Gas TURBANE Generater) working.plz explane
Dg pf .71 i am improve pf 0.80 what capacitor connected in dg how?
What is d main advantage of using double circuit 3 phase transmission ?
Is there any rule to select the voltage of motor based on KW rating? What is the rating above which lt motor becomes the HT motor?.
What happen if we apply square wave or traiangular waveform voltage to the transformer primary winding instead of sinusoidal wave?
how to calculate the distance relay faulty zone?pls explain?
how can i determine the KVA/MVA rating of transformer precisely?? is there any standard test?????
What is the bundle conductor?
what is the transmission loss for electrical supply? specifically a large shopping complex where the grid is half KM away, what will the % of transmission loss? is there any transmission loss for captive unit generation for above set? thanks
why current is constant on d.c?
Why does inductive loads consume KVARs?
rajha power sector details
what are the range of memory address in plc for L&T lx7 4A