I have 2 transformers in two different plants, both are
without OLTC but i am facing problem of voltage fluctuation
at LV side from only one transformer.
i have to change its taps manually twice in a day.
Another transformer delivering voltage is ok.
Please guide me about the problem
Answer Posted / 7anoter4
Voltage fluctuation it means voltage drop. It could be a
lot of factors producing big voltage drop.
The voltage drop in transformer -transformer size does not
fit the load and then at load peak the voltage drops under
the permissible limit and in less-or no load-the voltage
raises up to the secondary EMF [no-load voltage]- mainly if
there are many motor starts per hours.
If the supply-medium voltage-is variable-medium voltage
cable too small.
If the feeder from transformer to switchgear is undersized
the main voltage drop could be here.
A complete analysis could find the cause.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
what is high and low cut off voltage of BB and DG at SPS????????
Hello sir, pls send me hpcl technical test papers .i am. Appearing for the exam.
Which types of gate insttaled in static switch. Please give me answer.
what is the vvvf in the dumbwaiter?? or lift. what is the actual process?/
details of oil cell size of Breakdown voltage test of tranformer oil details as per Standardswith mushroom electrodes?
how to select electrical equipment such as fuse,dg,transformer,motor,msb,wire,cable as per the connecting load..please mention any books to design,take licence
Define settling time.
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
How to Preparation of online test
what is the importance of earthing system on the generators big capacity and small?
what kinds of Transformer oil grade is better for power transformer ?
xfhnchncv?
for 100 HP Induction motor service factor is 1.2(SF) we placed a VFD at the motor side load is balance with 0.3 Amp's Phase to Phase but at incoming of VFD load is un-balance with 10 to 20 Amp's what will be cause of load un balance
why -48 volts dc used in telecommucation
how to calculate the formula of cable size if motor kw is given