in which direction real power and reactive power flow and
why???????
Answer Posted / raul
Active power flow is proportional to the difference in the
load angle from sending and receiving end. i.e. the active
power flows from the higher load angle to lower load angle.
And similary the reactive power flow is proportional to the
diffence in the voltage levels from the sending and
receving end i.e. the lagging reactive power flows from
higher voltage level to lower voltage level.
During ferranti effect, the lagging reactive power demand
is lesser than the generation and hence the receving end
voltage is higher than the sending end voltage, so the
lagging reactive power flows from receiving end to sending
end.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What is Antipumping Function & If we have C.T how we find the Ratio ?
in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?
What is the problem of internal failure in ship engine telegraph system norcontrol?
how to copy from plc ge fanuc versamax series,all input and output, adress, and printout.
why we use ac supply as 415 volts instead of 415 v why we cant apply 230 v for dc
what is the reactive power what is the use of it in system
what is the relation between reactive power and power factor for the what is the limit of reactive power and power factor
what is the effect of un-synchronized power.
How we can recongnise the phase displacement of transformer connection between primary & scondary...plzzz explain it with example.........
What is the difference between earth fault protection of motor feeder with CBCT and Without CBCT ?
what is basic difference betmeen normal & flame proof motor??
how to calculate maximum current
Why synchronous motor is used in power factor improvement,dc series in lift
why does the magnetic balance tests at transformer?
At what factor resistance r of a conductor depends?