What is the harm if we install primary side 11 KV VCB at a
distance of one Km from the 11/3.3KV 12.5 MVA transformer
through 11 KV cable.
Answer Posted / darklord
No immediate harm ,but during maintenance this 11kv line
between VCB and transformer need to be discharged with out fail,
Also during switching action their would be switching surge
created due to oscillating of wave between vcb and
transformer which will heat and may damage insulation of
transformer.
Their would also be control voltage drop for 1000mtr wire
which will have significant effect on protection of transformer.
but proper control strategies will sort this problem
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
if grounding is notdone at regular intervals for long distance transmission, will the load connected at distribution end receive voltage during negativehalf cycle of the sine wave?
what are the things that can cause a three phase motor to crawl?
please tell me, how i clear the objective test? when i studied form the one book after i solved the objective ,that time i solved that qes. but if i tried solve objective form the other book then i could not solved these que.
What is Fire Panel ? How it works ?
Which types of gate insttaled in static switch. Please give me answer.
What should be setting for alarm,tripping and cooling fan on for power transformer's oil temp. and winding temp. indicator?
is it possible to say motor horsepower number without seeing name plate(when name plate damaged)
Parts of machine and their discription in details with suitable photo
While testing a ZCT what parameters have to check or measure?
what is transformor oil gread
I Just want do EHS Certified Certification Distance Course From Govt approved,so can any body provide me details.
How to do cable sizing calculation for 750 A Neutral Earthing resistor for 33kv. the 33kv cable going to swbd. is 630mm2 3 runs.
Ratings of power transformer,Distribution transformer.
What's the difference between non break power supply and non break non short break power supply
Swg formulae