Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I HAVE PRESSURE TRANSMITTER WITH TWO WIRES 24 VOLTS SUPPLY.IF
TRANSMITTER WILL GIVE SIGNAL TO THE DCS WHAT HAPPEN TO THE 24
VOLTS POWER SUPPLY IT WILL DROP OR REMAIN TO 24 VOLTS POWER
SUPPLY.

Answer Posted / carl_ellis

You describe a situation with a 24Vdc power supply, a 250
ohm dropping resistor and a 2 wire loop powered transmitter
at 4.0mA

To get the voltage to vary across the transmitter, you have
to change whatever the transmitter is measuring to get its
output to change, or force an output with a HART
communicator. The loop current does not vary on its own,
it varies in response to whatever the transmitter is
measuring.

Carl's Loop Rules

The voltage across the power supply remains constant: 24Vdc

The voltage drops across the transmitter and analog input
vary with the current in the loop.

Assuming a bench setup with very short wire runs and a very
low wire resistance, then if the analog input dropping
resistor is 250 ohms, then

at 4.0mA the transmitter drops 23.0V, the AI resistor drops
1.0V

at 12.0mA the transmitter drops 21.0V, the AI resistor
drops 3.0V

at 20.0mA the transmitter drops 19.0V, the AI resistor
drops 5.0V

The sum of the voltage drops must equal the power supply
voltage.

You can bank on it.

Carl Ellis
Measure First

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

principle of dead weight tester ?

2002


What is furnace draft control?

1025


flow transmeter accuracy 0.075% of full scale & find ucertainty is 0.025 % so what is maximum limit band of uncertainty

2254


Why is the orifice tab provided?

1144


what is RTV function in in process control?

3050


what is vibration a part of proceess variable? if vibration is a part variables then how we minimize the actual vibration on machine on load,? vision of instrumentation contrl plz ans me IPGDL interview question

1868


field bus transmitter calibration procedure tell me

1771


it is possible to check the fail safe condition in pressure transmitter. if possible how?

1339


Punj lloyd is coming in our Jadavpur Universtiy campus for campus placement. Please send me some hints about the writtend exam. My email id is subratafriends@gmail.com

2793


hii my name is sujith...i am preparing for HPVL GET 2010... so ,,,pls help me by send any previous questions or material to my site.....(Msujith_12@in.com) thank q

1828


on interface level transmitter model(RTG3302-EMERSON) What is threshold valve how can we select correct threshold value T1,T2,T3,T4 When interface water & hydro carbon

2099


How to decrease opening & closing time of on/off valve?

1441


how to control pid

1858


CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?

1843


can any send me a forbes marshall dtron 316 manual

1897