Answer Posted / raj
before doing tan delta test, just we know that its for
determine the condition of insulation to the equipments.and
it has more benefits when compared to meggering(IR).megger
means to find insulation only behinds surface condition.but
for tan delta/dissipation factor/loss factor/power factor
is to determine internal void conditions, and their
capacitances.
permissible limits of tan delta for all bushings - 0.7%
then important one while testing of tan delta, we should
take the current test temperature, then correct that one to
20*c. . .
for that correction we should take the values from the
correction table that we do by using specific testing kit.
for megger make,doble,eltel we have different tables. just
refer and correct it.
impt: it will be compare with factory reports only after
correction of values to 20*c
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?
can anyone send me some sample question regarding power grid corp
why do we have spikes enough to burn electronic boards, when generators are not grounded
Comment on the working principle of operation of a single-phase transformer.
What are the section criteria for cables. Now everywhere XLPE power cable is used or PVC is also used?.
if 2 coil of 1000W connect in series and 200 v is applied across it . then what is the total power of coil when coil have only resistive load .
11 kv input, 66 kv input advantages
What is relation between transmission lines & Communication lines ?
What will be the output voltage of a transformer if it is primarily energized from a square wave voltage source?
A system absorbs 100 k J of heat and the increase in its internal energy is 100 kJ; the work done is
iam preparing for rrb section engineer post in electrical branch.suggest the right textbook for my reference.fromwhere i will get the previous q.papers?
what are the assumptions made in swineburne's test?
Please brief working principle & construction of permanent magnet AC Servo motor
can any one suggest me the tilt angle of my solar pannel ?? or tell me how can i know the fix tilt angle of my solar pannel?? my cordinates are 31.503629,72.993164.
what is basic difference betmeen normal & flame proof motor??