Diff between Earthed & Unearthed cable ?
Answer Posted / mds.1490@gmail.com
n 3phase earthed system, phase to earth voltage is 1.732
times less than phase to phase
voltage. Therefore voltage stress on cable to armor is 1.732
times less than voltage stress
between conductor to conductor. Whereas in unearthed system,
(if system neutral is not
grounded) phase to ground voltage can be equal to phase to
phase voltage. In such case the
insulation level of conductor to armor should be equal to
insulation level of conductor to
conductor.
For example for a 6.6kV ungrounded system, 6.6kV/6.6kV (UE)
class cable has to be used while 6.6kV/3.8kV (E) class
cables are adequate for solidly earthed systems. The
UE-class cable is
naturally costlier than the earthed class of cable.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Explain what is electric traction? Explain few advantages of electric traction system?
what is sevice settings for mccb?How can be it setted?
what is a bus riser in power system and why it is used
what is mean by drives?
i completed my DEEE. and i want to electrical c license. how to get it..?
What is the name of the winding to which supply is given?
Hi, My plant daily consumption is calculated as 3.8MWH but my supplier has sanctioned an power of 2.6MW per day. how can i equal or distinguish this two factors
What are the symptoms of a bad PG card of a drive (inverter) esp. of Yaskawa Ac Drives (inverters) G7 ?
explain supply side and demand side energy management with advantages & disadvantages
I have finish diploma electronics and five years experience in electrical field in ht service how can i get c licensce or other electrical certificate
why output is out of phase in case of common emitter?
why swityard is necessrry requirement in any bis power distributin systems?
why we have and use 3 phase not 2 or 4 or other in power system?
Can you explain about pole discrepancy scheme
What is the rating of a circuit breaker needed for 300 kv load in 33KV supply line of 33/415 transformer ? Whether 800/1200 amp vaccum circuit breaker can perform for a 33 KV line in input in 415 volt in output of the transformer ?