Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...



Diff between Earthed & Unearthed cable ?

Answer Posted / mds.1490@gmail.com

n 3phase earthed system, phase to earth voltage is 1.732
times less than phase to phase

voltage. Therefore voltage stress on cable to armor is 1.732
times less than voltage stress

between conductor to conductor. Whereas in unearthed system,
(if system neutral is not

grounded) phase to ground voltage can be equal to phase to
phase voltage. In such case the

insulation level of conductor to armor should be equal to
insulation level of conductor to

conductor.




For example for a 6.6kV ungrounded system, 6.6kV/6.6kV (UE)
class cable has to be used while 6.6kV/3.8kV (E) class
cables are adequate for solidly earthed systems. The
UE-class cable is
naturally costlier than the earthed class of cable.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is difference between elr and R eartl realy.

2699


what is the meaning of number in (11, 31, 61,14, etc. CDG11, CDG31, CDG61, DDT32

1489


what is the thumb rule for determination resistance of resistor?

2366


what is the safe meggar values for motor, transformer HT, LT and Cables? IF we want to replace I/C bay at our 220 kv substation which is of 140 mw load capacity bay to be replaced by 400 mw capacity bay.other than CT(1200/1) what are the other equipment i have to replace. why we generally use 3.5 core cable or in other word 1/2 core for neutral and also confirm me that in balance conditiob(3 phase)current in neutral will zero

2319


wheather the size of windings in motor and generator are the same

2054


Dear Sir/Madam, I have one questions we have three steam turbines and one Gas turbine and our industry linked with the public network, we have protection system one of the protection is reverse power we can export just four MW only i would like to ask about how to calculate the reverse power. Thank you in advance best regards

2137


what is the chemical name and formula of refrigarent R-134a.

2338


Main advantage of auto transformer over two windings transformer is that A it needs no cooling B it uses only one winding C core losses are reduced D it has simple construction

2984


What are the limitations of Kirchoff's laws?

1642


What is the different between conventional MCC and intelligent MCC? Common controller or controller for each bucket

1115


what happen if the load connected to the induction motor is taken away? the same question for synchoronous generator in synch i think that the the exitation voltage will appear on the terminal only if so plz answer me

2058


how to find motors H.P. whout any rating? (only give you a motor and multimeter)

6223


how to calculate IR value of 33KV cable ??

1980


why does a dc machine has high efficiency while working as a generator than as a motor ..

2050


THERMAL CAPACITANCE IS MEASURED IN..................................................

2199