Answer Posted / sakthi
Internal
Winding Phase-Phase,
Phase-Ground faults
Differential (87T), over current (51, 51N)
Restricted ground fault protection
(87RGF)
Winding inter-turn
faults
Differential (87T), Buchholz relay,
Core insulation failure,
shorted laminations
Differential (87T), Buchholz relay,
sudden pressure relay
Tank faults Differential (87T), Buchholz relay and
tank-ground protection
Overfluxing Volts/Hz (24)
External
Overloads Thermal (49)
Overvoltage Overvoltage (59)
Overfluxing Volts/Hz (24)
External system short
circuits
Time overcurrent (51, 51G),
Instantaneous overcurrent (50, 50G)
Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
In cable sizing calculation (determining the max route length of cable) why we choose the shortest length between cable length of full load current Iflc & starting current Istart?
What are the Formula of computing Back up Time of 500kVA UPS with 4 Battery Banks, each bank composed of 43 pcs of Batteries 12V150Ah. How to compute the Back up Time of UPS? We have also 3X500kVA UPS running in Parallel same composition as I write above.
How relay coordination has to be done? what are the inputs are required for this? Please explain this with calculation method?
How to select the proper VSD to operate high inertial load
What are the classifications of heating element?
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
What is the difference between shortcircuit current, rated current of cable & MCB with example? What will be the size of cable required for 5.5 KW motor (Full load current 10 Amps approx.), Starting current with DOL is 120 Amps. Aprrox. Short circuit current with LLLG fault is 2000 Amps Approx.
What is the breaking capacity of transformer and how can we calculate the breaking capacity of tranformer
What is servo lock in CNC how they work and if any parameter for them in CNC machine
Why electrical power generation and transmission done in 3 phase system not more than 3 phase ?
11 kV line deraction check by an Engineer.
If a current -8+6sin6t is flowing three ammeter, one is a centre zero PMMC meter, one is true rms meter and one is moving iron meter. What are the reading of these three meter respectively?
how to calculate differential current when we testing differential relay..suppose we have 1000kw generator,630amp VCB,what value we should put /inject so that relay trip the VCB? PLLZ justify ur comment
difrent between vcb acb sf6 and mccb breakers
what is settable hystersis protection? If any body knows plz kindly post the answer..