Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

HOW TO CALCULATE UPS BATTERY BACKUP TIME

Answer Posted / m.b.parthasarathy

The formula is as follows.

1. To find battery back up time : Battery AH X Battery volt X constant factor is divided by load(in watts). Perhaps if you have 100ah battery and the load is 500watts you can find back up time as follows.
EX: 1ooAH X 12V X 0.85 / 500
100AH X 10.2 / 500 = 2hrs.

2. To find battery AH : Back up time X load is divided by Battery volt X constant factor.Suppose you need 2hrs back up time with 500watts load, yu can calculate battery AH as follows.
EX: 2 X 500 / 12 X 0.85
1000 / 10.2
= 98.03AH. Commercially available 100AH battery only.

Is This Answer Correct ?    8 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Anybody tell me about modbus hex address of l&t trivector meter er300p??I want to read voltage,current,kwh etc via rs485...If anybody have a manual then send on my mail..Brijeshmodi18@gmail.Com

1912


What is mean by STUB protection?

2068


Assuming that a dedicated neutral earthing transformer is provided for each GT generator, when the two generators are running in parallel, has consideration been given that the earth fault current from one generator stator winding be split between the two neutral earthing transformers? If so, what adverse impact will this have on the operation of the 59N and 27TN devices?

1666


what is effect of 5amp fuse on 2mva pry protection of transformer

1857


hi frnds...pls send me aptransco previous papers .....pls..pls,,,(madhar.rocking@gmail.com)and suggest me some websites

2132


Earth leakage relay basic knowledge principle

2191


what is the illumination level required for child play area?

2101


explain me the relation between torque, frequency,speed,voltage and current in the 3 phase induction motor?

2264


Whether amorphous core transformer is available in India?.If available then up to what rating of voltage and KVA?.

1746


Why there are some equipment(i.e:TV) that using 2-pin plug instead of three? What happen if there is current leakage? Are we going to get electric shock??

2198


what is 400kv doble circuit quadpole tower?

1950


How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?

1084


how we can come to know that motor winding resistance which showing by DMM is right or wrong???is there any chart or something that we will compare & check???

1915


HOE WE CAN IMPROOVE BY USE OF CAPACITOR

1969


1) Explain why we don't link the two earthing system ht and mv on a pole mounted transformer sub-station.

1799