HOW TO CALCULATE UPS BATTERY BACKUP TIME
Answer Posted / m.b.parthasarathy
The formula is as follows.
1. To find battery back up time : Battery AH X Battery volt X constant factor is divided by load(in watts). Perhaps if you have 100ah battery and the load is 500watts you can find back up time as follows.
EX: 1ooAH X 12V X 0.85 / 500
100AH X 10.2 / 500 = 2hrs.
2. To find battery AH : Back up time X load is divided by Battery volt X constant factor.Suppose you need 2hrs back up time with 500watts load, yu can calculate battery AH as follows.
EX: 2 X 500 / 12 X 0.85
1000 / 10.2
= 98.03AH. Commercially available 100AH battery only.
| Is This Answer Correct ? | 8 Yes | 3 No |
Post New Answer View All Answers
Difference between transition and diffusion capacitance
how to calculate the loss tangent of electrical cables
At what speed 1 HP motor can run an electric car of weighing 400 kg?
is it possible to say motor horsepower number without seeing name plate(when name plate damaged)
What are merits & De-merits of State-Space Method? What is series programming, parallel programming, general programming & direct programming ? And, difference between these programmings Techniques ?
Explain Even and Odd signals?
On a 3 winding transformer YNynd11, how do you apply REF protection to the Delta tertiary winding that is supplying auxiliaries to a substation?
I completed iti in2004 I was worked in A grade contractor can I get c licence
Define phase lag and phase lead?
i am completed diploma in ece,and working in ht and lt lines.so is elligible diploma in ece for get electrical C Licence?plse give ur opinion?
Please brief me about number of pole in alternator.In single phase alternator coils are connected in star or series. How to calculate frequency for the same.
What is the theoretical reason for the size of a zig zag grounding transformer to be 1.732 times less than that of a wye-delta grounding transformer used for the same application?
What happens to a motor if it is connected in Delta connection
can any tell me why slope 40% and 80% is calculated in differential protection?
how are reversing the direction of dc motor