HOW TO CALCULATE UPS BATTERY BACKUP TIME
Answer Posted / m.b.parthasarathy
The formula is as follows.
1. To find battery back up time : Battery AH X Battery volt X constant factor is divided by load(in watts). Perhaps if you have 100ah battery and the load is 500watts you can find back up time as follows.
EX: 1ooAH X 12V X 0.85 / 500
100AH X 10.2 / 500 = 2hrs.
2. To find battery AH : Back up time X load is divided by Battery volt X constant factor.Suppose you need 2hrs back up time with 500watts load, yu can calculate battery AH as follows.
EX: 2 X 500 / 12 X 0.85
1000 / 10.2
= 98.03AH. Commercially available 100AH battery only.
| Is This Answer Correct ? | 8 Yes | 3 No |
Post New Answer View All Answers
Anybody tell me about modbus hex address of l&t trivector meter er300p??I want to read voltage,current,kwh etc via rs485...If anybody have a manual then send on my mail..Brijeshmodi18@gmail.Com
What is mean by STUB protection?
Assuming that a dedicated neutral earthing transformer is provided for each GT generator, when the two generators are running in parallel, has consideration been given that the earth fault current from one generator stator winding be split between the two neutral earthing transformers? If so, what adverse impact will this have on the operation of the 59N and 27TN devices?
what is effect of 5amp fuse on 2mva pry protection of transformer
hi frnds...pls send me aptransco previous papers .....pls..pls,,,(madhar.rocking@gmail.com)and suggest me some websites
Earth leakage relay basic knowledge principle
what is the illumination level required for child play area?
explain me the relation between torque, frequency,speed,voltage and current in the 3 phase induction motor?
Whether amorphous core transformer is available in India?.If available then up to what rating of voltage and KVA?.
Why there are some equipment(i.e:TV) that using 2-pin plug instead of three? What happen if there is current leakage? Are we going to get electric shock??
what is 400kv doble circuit quadpole tower?
How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?
how we can come to know that motor winding resistance which showing by DMM is right or wrong???is there any chart or something that we will compare & check???
HOE WE CAN IMPROOVE BY USE OF CAPACITOR
1) Explain why we don't link the two earthing system ht and mv on a pole mounted transformer sub-station.