how much current capacity of 300 sq. mm cable (4 core
aluminium) and 150 sq. mm cable ( 4 core aluminium)
Answer Posted / 7anoter4
It depends on lot of factors. The duration of the load:
short-time[as in short-circuit case],continuous load,
intermittent load. It depends on also on ambient type [air,
underground-direct laid or in concreted duct],on thermal
resistivity of the ambient [if it is in underground],on
ambient temperature, on insulation type[bare, pvc, xlpe,
epr etc.] and other factors.
Let's say in short-circuit case for 1 sec 300 square mm
aluminum conductor pvc insulated. Permissible temperature
[for PVC short-time]= 150oC.Ambient air 30oC.
Ipermissible=27 kA[27000 A].
For the same cable in open air 30oC[NEC Table 310.15(B)
(17)] continuous load [75 oC]600 MCM=300 sqr.mm permissible
545 A
| Is This Answer Correct ? | 1 Yes | 3 No |
Post New Answer View All Answers
how we can set the IDMT relay.
how can motor both beasrings insulation resistance can be check?
how much leakage current is allowed in MC61A L&T make relay?
what are the factors to be considered while design the breaker either HT or LT??
what is ps impedance test
What is Control & Relay Panel? And Remote Control Center?
how calculate gd2 of ht motors
What is resolver and glass scale in CNC how they work?
If you have an earth with pilecap then your resistance is really low. why and how?
Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?
what are the stresses in circuit breakers ?
if two transformers are placed parallel & both have fault impedance of 50KA will it increase or decrease show example?
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
Which contains in POLE ASSEMBLY of a 11KV Kirloskar-make SF6 (Model No-FP620A12)? Will u clarify with drawing?
why 1.7Uo for HV cable Hi pot test?IE standard why?