Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why we use 24 vdc in instruments mostly?

Answer Posted / carl_ellis

There is no national or international standard for 24Vdc in
industrial instrumentation and control.

The use of 24Vdc has evolved out of common practice and has
seen global use and acceptance as a 'de facto' convention,
as opposed to a formal standard. The acceptance goes
beyond loop powered transmitters, it goes into discrete
control as well.

The reasons are many.

1) 24Vdc is a low enough voltage to be considered 'safe'.
It is accepted as a voltage level that does not shock human
beings through contact with dry skin.

2) 24VDc is a high enough voltage to do real work with
currents that are practical.

3) An enormous array and variety of field instruments and
controls can be designed and operated intrinsically safe at
24Vdc, not just loop powered transmitters.

4) Loop powered field instruments powered by 24Vdc can
drive 500-600 ohms of load resistance, enough for one valve
positioner (split ranging 2 valve positioners with a single
current output driven by 24Vdc is difficult).

5) Lead acid batteries are useable for battery back-up or
UPS supplies.

6) On the discrete side, 24Vdc is sufficient voltage to
break through oxide coating on switch and relay contacts

7) For discrete control, 24Vdc offers a tolerance band
around binary 'high's and binary 'low's of more than a
couple volts, which allows for operation in a moderate
level of electrical noise.

8) Statistically, 24Vdc devices have failure rates about
half of that of 120/240Vac actuation devices (relays and
solenoids). This a serious consideration for emergency
shutdown or SIS systems.

Carl Ellis
Measure First

Is This Answer Correct ?    10 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?

2391


What is the difference between ff transmitter and non ff transmitter

2434


What is the basic difference between Modbus and CAN Open Protocols

6427


hi! i want to know about mpse exam.

2277


what is the vital subject for scoring bhel exam&what is the question pattern

2392


What is the exact differences between HART,FOUNDATION FIELDBUS,PROFIBUS?

3446


what is the input of digital counter during the the calibration time?

2307


How to Calibrate Flow Switch in field

1248


In turbine what does term CDP, NI, NH, HSSOC means.

2567


defination of radial vibration?

2259


What is feed factor and its Importance in cement industry? How we can solve feed factor?.

3597


How to Calibrate Vortex Flow transmitter in field

1262


Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,

1679


what is insdustrial vibration.who it works. give atleast 2 types of insdustrial vibration

1961


In Safe Guarding test what means by "Failed to Danger" ?

2146