How to calculate incomer of a capacitor bank/feeder from its
KVAR,
AND how to calculate the copper busbar for rated incomer,like
for 400A we calculate the 40x10 of aluminum busbar.
Answer Posted / 7anoter4
If the system is three-phase: KVAR=sqrt(3)*Icap[A]
*Volt/1000 then:
Icap=1000*kVAR/Volt/sqrt(3)
If the ambient temperature will remain the same and if
permissible conductor temperature will be the same then
copper bus bar cross section required will be 70%[approx.]
from Aluminum bus bar.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is a commutator?
WHY THREE PHESE SYSTEM VOLTAGE APPLIED IN 440 VOLT
hello! sir i did three year of diploma in electrical (2007- 2010) and now i m a student of electrical engineering. sir can i apply for germany visa for study and part tome work over there?
lorteny method
When the relative speed between the magnetic fields of stator and rotor does is zero under steady state operation?
Should power factor be low or high?
If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..
How cmd is calculated in case of energy neters
what is the difference between oil surge relay and buchholz relay.
What si the d/f b/w KVA & KWH, kvarh & kvar, kwh & kvar phase voltage & line voltage
What is the formula to calculate the rating of a three phase air circuit breaker
how balanced in star delta connection ?
How to calculate the External Resistance required for 60HP slipring motor in case no any data of the Motor is available???
The 3 phase 400 hp 440 volt slip ring induction motor do not take one phase amps why ? The motor is running good condition
How to calculate mf when meter equipment and meter are connected