How to calculate incomer of a capacitor bank/feeder from its
KVAR,
AND how to calculate the copper busbar for rated incomer,like
for 400A we calculate the 40x10 of aluminum busbar.
Answer Posted / 7anoter4
If the system is three-phase: KVAR=sqrt(3)*Icap[A]
*Volt/1000 then:
Icap=1000*kVAR/Volt/sqrt(3)
If the ambient temperature will remain the same and if
permissible conductor temperature will be the same then
copper bus bar cross section required will be 70%[approx.]
from Aluminum bus bar.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
can anybody sent me power grid questions. what subject should i prefer for preparation?
What do you understand by external characteristics of a d.c. Generator?
What is the working mechanism of OLTC in Power Transformers????
In a large office how do we calculate required number of light fittings, assuming fittings are 4x18W or 2x36W fluorescent fitting ?
A 3 phase transformer's (Y-Y) Y and B phase is (Y and B connection not broken) broken from neutral and R and Nutral connection is ok, what will be the relay tripping and why
in electrical control panel. how can i choose the cable rating. (example - 11kw motor, 18-25A mpcb}
why induction motors are rated at 0.8 power factor.
how to calculate IR value of 33KV cable ??
What is kirchoff ’s current law (kcl)?
how to measure dc earth leakage current?
How vfd saving power.
details of oil cell size of Breakdown voltage test of tranformer oil details as per Standardswith mushroom electrodes?
Please tell me the formulaes while designing a substation for power Calculations in designing a 33 KV Substation?????
3phase cable calculation formula by motor load
Is Transol transformer oil comparable to nynas nytro libra?