In power generator sets, when they are coverted from 50hz
to 60hz, the kva rating after conversion increases. For
example, the manufacturer of a perkins 200kva @ 50Hz
generator set has mentioned it to become 220kva after
converstion to 60hz. What is the relation between the
frequency & the KVA rating. Any formula please.
Answer Posted / kj
The main reason for the increase in the kva is that the
diesel engine produces more HP at 1800 rpm than at 1500 rpm.
This allows a higher kw output. The alternator can also
handle the higher current and therefore the kva is
increased. Note that the rated power factor stays the same.
This is because the amount of cooling air is increased at
the higher speed.
The increase in the EMF per turn allows a higher voltage to
be generated but this is reduced by the AVR reducing the
excitation. This has no effect on the kva capacity of the
generator set.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What are the types of windings present in the ceiling fan? What winding will be effective first when we started the fan?What are the resistance and inductance ratios comparatively at the initial speed and full speed of the fan?
Why human body feel electric shock?
What are the three major categories of error?
What are the advantages and disadvantages of the dc motors?
What fomula is used to calculate: 1. rated frequency withstand voltage, and 2. rated lightning impulse withstand voltage.
sir, 3phase induction motor takes different pf and different KW in three phase while running,explain reason
Please explain, how to test vector group of tranformer(Delta y1) . Thank
Can anyone please provide me details of MCCB/Contactor/SFU rating calculations for a motor feeder..for example 50 kw.. not from type-2 cordination chart. i want manual calculations..
11 kV line deraction check by an Engineer.
Post possible questions for Power Factor Panel FAT / SAT
What are the protections for safe running of electric generator?
WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.
briefly explain principle of resistance welding
what is earth resistance? how to measured? and give values at power station and mcc area?
We have a distribution transformer of 750KVA/11kv/440v and an AVR (Servo Stabilizer) of 750KVA on the LT side of distribution transformer. Also we have an ACB of 1200A on the output of distribution transformer (that is on the input of AVR). We want to have an MCCB on the output of AVR. What should be the rating?