Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why CT ratio stand for 50/5, 100/5, 25/5.

Answer Posted / madhu

Generally allThe CT operated meter is designed for a
capacity arround 5 A , the ct ratio 50/5, 100 / 5 means the
secondary current of the secondary winding will not exceed
more than 5A.Our kwh meter capacity max 5A so consumers more
requirement ex- 50A consumer load so our kwh meter not
measured the reading that cases using ct .ex 50/5 50a flows
in a line meter shows 5A its ratio 50/5 = 10 so ct ratio 10
ex our units 12/day multiply by 10 = 120 units/day

Is This Answer Correct ?    10 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

hi friends how 3 phase converter functioning ?what is working principle of rotory phase converter ?

2158


on a three-winding transformer relationship delta-delta-star, on third winding why the relationship is a star? what are the advantages and disadvantages? Thank you and please help

1774


WHAT IS THE DIFFERENCE BETWEEN AN ACB & mccb 7 WHAT IS THE CRITERIA WHEN TO USE WHICH OF THE TWO

2370


As per standard, transformer body earthing and other Equipment earthing (Equipment earthing) did not connect. but in LT side termination we are doing metal glanding in both side Transformer to PCC Panel through armoured cable, now X'mer body earthing and PCC Pane earthing (Equipment earthing) both are connect.is this safe for X'mer or other equipment?

1812


What are the criteria shall be considers for sizing Fuse and MCB? If the rated current is 10Amps what should be the fuse size / MCB Size?

1701


300m long and 30kw inductive loade 3phase supply how many size cable required

1483


ho can we calculate the conductor insulation value according to their ratings like voltage,current etc.how insulation value related with voltage,current and power of amachine

2154


what is the transformer turn ratio formula and give some examples?

2479


Define cut-off rate?

1133


What is the disadvantage in proportional controller?

1188


Readings of ER300P Trivector meter

6463


We have studied about many techniques for finding the stability of system, ROOT LOCUS, ROUTH, BODE PLOT, POLER PLOT etc. In these which is used where. what are the difference among them... PLZ tell me.......

2265


What is the kiosk parts, about them and their functions ? If anybody have some PDFs files or details about this plz send it on tawhidfaisal@Yahoo.com

1978


how can found motors folt current ? how can disided circuit breakers caoicity and breaking capicity ?

2223


while starting a liquid starter ,is there any volage drop on water/soda on tank.can we touch the tank on starting?

1964