the inertia constants of two machines are respectively 30and
42 MJ per MVA.when the change in frequency due to change in
load in first machine is 12 Hz,the change in second machine
frequency will be?
Answer Posted / 7anoter4
If the change in load will be the same Pa1=Pa2 and the
rated frequency fo1=fo2
for the same time interval dt1=dt2
IF Pa=H*MVA/180/fo*d2R/dt2 [See IEEE-399 ch. 8.6.2 How
stability programs work]
and d2R/dt2=2*pi()*df/dt
then (df/dt)1=Pa/2/pi()*180*fo/MVA1/H1 and
(df/dt)2=Pa/2/pi()*180*fo/MVA2/H2
(df/dt)2/(df/dt)1=MVA1*H1/MVA2*H2
If MVA1=MVA2 then (df/dt)2=(df/dt)1*H1/H2
df2=12*30/42=8.57 Hz
| Is This Answer Correct ? | 1 Yes | 10 No |
Post New Answer View All Answers
How does cost of generation from hydropower plant compare with other sources of electricity?
what is the efficiency of thyristor
Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output
how to determine the cable size...pls explain me with the formula taking particular load....does the factors like impedance & short circuit rating influence the cable size, if so how....
Draw a block diagramof Three UPS systems connected in Parallel mode?
can we use ZNyn11 transformer instead of Dyn11 transformer in distribution for effectively eliminating harmonics from the industrial loads.
HOW DO I CALCULATE THE SETTINGS FOR THE DIFFERENTIAL PROTECTION OF A 12kV/6.6kV, 6MVA,DYN11 XMER WITH PRIMARY SIDE CTR 400/1 AND SEC SIDE CTR 600/1?
what is meant by 3rd hormonics ?
What is the difference between electronic regulator and ordinary rheostat regulator for fans?
I am having dual speed motor of cromton greaves make of 3.7 KW -1400 rpm and 5 KW - 900 rpm. Please let me know groups and winding connction for rewinding purpose.
When we use 3 terminal resistor?
What is the relation between frequency and motor rpm?
what is the power factor used by the PHCN in nigeria? 2. what is the difference between an alternator and generator. 3. Generation of poweris in KV but how is transmission is in MW. 4.If the transmission of power is 20,000MW how can it be increaesed to 80,000MW
Why is ignitor used in sodium vapour lamp
can i use 4 number of circuit breaker as single phase manual change over switch? if yes then how plz also send ckt diagram at nazimzamurad@gmail.com