what is the major difference between dc generator and
synchronous generator?
Answer Posted / 7anoter4
In three phase system the 3 phases windings are even
distributed along the stator periphery and since the 3
phase currents are 120 electrical degrees in time
distanced one from each other ,then an apparent rotating
magnetic field is installed[as an armature reaction].
The synchronous generator rotor rotates in the same time
with this field [stator itself does not move]. [differently
from the asynchronous[induction] generator in which rotor
velocity is more elevated than this field velocity and the
difference depends on the load.]
In d.c. generator no such rotating field is generated as
the armature reaction is always in d.c. field and it is
rotates with the rotor together[one could say it is
also "synchronous" rotation].
However this field disturbs the collector operation in the
commutation process.
In order to avoid this, commutation auxiliary poles are
located between excitation poles and are supplied by
armature current.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is meant by time harmonics and space harmonics?
why we have and use 3 phase not 2 or 4 or other in power system?
Give details on how you intend to handle a challenging position you are posted to manage unexpectedly as a company staff?
How to select batteries required for ups and the inverter if we Known load? And how AH is selected of battery?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
Define maximum demand?
what is a reactive power? what is the relation with power factor?
Why single phase induction motors are not self starting ?
In synchronous motor, how the field current is related to armature current..i know its inversely proportional..but concept wise...i was nt clear....pls help me...
Zone of protection and tripping scheme of arc protection relay.
describe the constructional features of an auto transformer and its principle operation
why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??
Why High voltage are generate noise ?
Capacitor is load free component but why ampere meter shows current when capacitor bank breaker close?
If we need 4c× 50mm sq cable but it's not available so we can pull 4c×25mm sq two cables?