How to calculate the value of capacitance of a capacitor
used in power factor improvement plant if we know KVAR and
voltages?
Answer Posted / raviteja vaka
for 3-ph system
Kvar=Sqrt(3)*v*i*sin(phi)
or Kvar=kw*tan(phi)
and for value of capacitance when kw or kvar is known
c=KVAR/(2*3.14*f*v^2) when capacitors are connected in Star
c=KVAR/(6*3.14*f*v^2) when capacitors are connected in Delta
I think the above information is in line with your question
If u want any further details mail me @ raviteja.vaka@gmail.com
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
What is routh hurwitz stability criterion?
how to setting voltage RTCC panel
What is the maximum percentage voltage drop (vd%)for a motor control center
how to select energy meter? have any calculation?
LET ME NOW MORE ABOUT icu and ics for circuit breaker. how we calculate the rating of circuit breaker and i c u and ics values
Load break swicth maintenance procedure.
our factory is going under construction mean time transformer 1000 kva 2 nos &load break swithch 12 kv & 4 nos 750 kva 2 nos & 380 kva 2 nos generator to be errcted.how to arrange earth pits &how to earth connect & neutral pit how to calculate in earth bit size.
is that a problem if i connect a single phase load to a secondry delta connected transformer but i get a neutral from other transformer i the system?
Enlists the applications of sampled data systems?
Sir, I have applied for the of Assistant.engineer of NPDCL. please send me all AP TRANSCO AND JENCO solved papers of previous exams . I requested send me the papers to my id as soon as possible (rajanikanth_peddi@yahoo.co.in) (This is very urgent) Thank You,
can anybody send me syllabus of rrb section engg (electrical). and also send previous question pepar...
working principle a.v.r. ?
75 kw motor take 45 amp in no load delta in star 10 amp but in load it will take 160 amp but IR velue of winding above 500 at 1kw ph to earth and ph to ph. what problem it should be?
what is level 2 automation?
What is the implications when 600 hp motor is started when the unit is running with Transformer of capacity 1500 KVA and DG set of 1000kva